Controller, except in the case of an alarm or service
reminder (see 5.b and 7.b in Alarm & Service Mode).
Display Mode is comprised of several screens (described
below). The controller automatically scrolls through the
screens, displaying each one for 4 seconds. The user can
override the 4 second time period and force the next screen
to be displayed by pressing S .
The screens are displayed in the following sequence: 1, 2,
3A, 4, 5, 6, 1, 2, 3B, 4, 5, 6, 1, 2, 3C, 4, 5, 6, 1, 2, 3D, 4, 5,
6, ... with the exceptions noted below.
7.10.1 Display Mode Screen 1 – Dew point class and cycle
type.
2: -40°C/-40°F
DEMAND CYCLE
7.10.2 Display Mode Screen 2 – Energy savings.
This screen is not displayed if FIXED cycle is selected.
ENERGY SAVINGS
XX%
7.10.3 Display Mode Screen 3A – Service reminder
(filters).
This screen is not displayed if 1 or 2 filter monitors are
detected.
HOURS TO SERVICE
FILTERS: XXXX
7.10.4 Display Mode Screen 3B – Service reminder
(desiccant).
HOURS TO SERVICE
DESICCANT: XXXX
7.10.5 Display Mode Screen 3C – Service reminder
(valves).
HOURS TO SERVICE
VALVES:
7.10.6 Display Mode Screen 3D – Valve cycle counter.
CYCLE COUNTER
XXXXXXX
7.10.7 Display Mode Screen 4 – Dryer outlet dew
point,(AUX2, analog input).
This screen is not displayed if jumper 3 is not installed.
OUTLET DEW POINT
±XX°C ±XXX°F
XXXX
7.10.8 Display Mode Screen 5 – Dryer inlet pressure,
(AUX3, analog input).
This screen is not displayed if jumper 4 is not installed.
7.10.9 Display Mode Screen 6 – Dryer inlet temperature,
(AUX3, analog input).
This screen is not displayed if jumper 5 is not installed.

7.11 Test Mode

Test Mode is active when the user exits Setup Mode after
selecting operation in MANUAL CYCLE.
Test Mode is comprised of eight screens (descriptions
follow the table below). Each screen corresponds to one of
eight program steps (described in the table below).
Press S to advance from one screen (program step) to
the next. Be sure to read and understand all cautions listed
with the screen (program step) descriptions.
If the temperature is below 40°F or the thermistor circuit is
open, the second line of the display will read "UNDER-
RANGE" instead of the temperature reading. (Refer to
screens 2, 3, 4, 6, 7, and 8.)
If the temperature is above 150°F or the thermistor circuit is
shorted, the second line of the display will read "OVER-
RANGE" instead of the temperature reading. (Refer to
screens 2, 3, 4, 6, 7, and 8.)
Upon entering Test Mode, the program can be at any one
of the eight steps.
To exit Test Mode:
1.
Use S to manually advance the program to
step 1 or 5.
2.
Press and hold E for 3 seconds to exit Test
Mode. The display switches to Screen 2 of
Setup Mode.
3.
Use S to select DEMAND CYCLE or FIXED
CYCLE.
4.
Press E to accept the selection and
activate Display Mode.
- 35 –
7. Controller – Level 2
INLET PRESSURE
XX BARG XXX PSIG
INLET TEMP.
XX°C XXX°F
a)
The program must be set at step 1
or 5 to exit Test Mode.
b)
Screen 9 is displayed for 3
seconds if the user attempts to
exit the program from step 2, 3, or
4.
c)
Screen 10 is displayed for 3
seconds if the user attempts to
exit the program from step 6, 7, or
8.
7. Controller – Level 2