Function settings (continued)
Note;
The ventilation mode follows the table below.
Interlocked air conditioner
Energy recovery
ventilation mode
Either Yes or No
By-pass ventilation
mode
Cooling/Stop
Automatic
Other than above
Automatic ventilation mode setting 1)
No.52
Outdoor and indoor temperature gap
temperature gap between indoor and outdoor.
This function is available when setting Data 3 is selected at function
No.
51.
Setting
check
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
N/A
52
-
-
-
-
-
-
-
-
Automatic ventilation mode setting 2)
No.53
The lowest outdoor temperature
minimum outdoor temperature which comes in indoor directly.
This function is available when setting Data 3 is selected at function
No.
51.
Setting
check
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
53
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Eng-18
Energy recovery ventilation
mode
By-pass ventilation mode
Always energy recovery
ventilation mode
Setting
Indoor temperature -
check
outdoor temperature
0
1
2
3
4
5
6
7
Setting
Outdoor temperature
check
0
1
2
3
4
5
6
7
10
11
12
13
14
15
Automatic ventilation mode setting 3)
No.54
The lowest indoor temperature setting
minimum indoor temperature.
This function is available when setting Data 3 is selected at function
No.
51.
target temperature of the indoor unit is the lowest indoor temperature
for By-pass mode
Setting
check
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
54
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Free By-pass setting
User can set conditions to go into By-pass mode in automatic
ventilation mode by function
Setting examples are shown below.
Example 1*
By-pass/Energy recovery ventilation map in automatic ventilation
mode
40
Energy recovery ventilation area
38
36
34
32
30
28
Set by function
26
24
Set by function
No. 54
(Terget temp. of air
22
20
18
16
14
12
10
8
8
10
12
14
16
18
Function No. Setting Data
52
53
54
Setting
Indoor temperature
check
0
1
2
3
4
5
6
7
10
11
12
13
14
15
No. 52 No. 53
and
No.
54.
No. 52
By-pass ventilation area
Set by function
20 22 24 26 28 30 32 34 36 38 40
No. 53