Fujitsu WATERSTAGE WOYG112LHT Maintenance Document page 60

Air to water heat pump
Hide thumbs Also See for WATERSTAGE WOYG112LHT:
Table of Contents

Advertisement

Air to Water Heat Pump (Split integrated DHW type)
Line
Function
Generator diagnosis
8400
I
Compressor 1
8402
I
Electrical resistance flow 1
8403
I
Electrical resistance flow 2
8406
I
Condenser pump
S
8407
Speed condenser pump
8410
U
Return temp HP
Setpoint (flow) HP
8412
U
Flow temp HP
Setpoint (flow) HP
8413
U
Compressor modulation
8414
I
Modulation electric flow
8425
S
Temp diff condensor
S
8450
Hours run compressor 1
8454
S
Locking time Heat Pump
Reset ? (no, yes)
8455
S
Counter number of locks HP
Reset ? (no, yes)
8456
S
Hours run electrical flow
Reset ? (no, yes)
8457
S
Start counter electrical flow
Reset ? (no, yes)
8458
I
State smart grid
I
8460
Heat pump throughput
Diagnostics consumers
8700
U
Outdoor temperature
8701
U
Outdoor temp min
Reset ? (no, yes)
8702
U
Outdoor temp max
Reset ? (no, yes)
8703
I
Outdoor temp attenuated
Reset ? (no, yes)
This is the average of the outdoor temperature over a 24-hour period.
This value is used for automatic Summer / Winter switchover (line 730).
8704
I
Outdoor temp composite
The mixed outdoor temperature is a combination of the current outdoor temperature and the average outdoor temperature
calculated by the regulator. This value is used for calculating the initial temperature.
8730
I
Heating circuit pump, circuit 1
8731
I
Mixer valve HC1 open
8732
I
Mixer valve HC1 closed
8740
U
Room temperature 1
Room setting 1
8743
U
Flow temperature 1
Flow temperature setpoint 1
8749
I
Room thermostat 1
- 60 -
Setting range
or display
Off, On
Off, On
Off, On
Off, On
0...100%
0
140 °C
0
140 °C
0... 100%
0... 100%
-50... 140 °C
00:00
0... 2730 h
0
65535
0... 2730 h
0
65535
Draw disabled, Draw free,
Draw wish, Draw forced
0... 65535 l/min
-50... 50 °C
-50... 50 °C
-50... 50 °C
-50... 50 °C
-50... 50 °C
Off, On
Off, On
Off, On
0
50 °C
0
140 °C
No demand, Demand
Installation and operating manual "1768 - EN"
Setting
Basic
increment
setting
Off
Off
Off
Off
--
--
--
--
--
--
--
--
--
--
--
--
--
Draw free
--
--
50 °C
-50 °C
--
--
Off
Off
Off
--
20 °C
--
--
No demand

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents