Fujitsu WATERSTAGE WOYG112LHT Maintenance Document page 50

Air to water heat pump
Hide thumbs Also See for WATERSTAGE WOYG112LHT:
Table of Contents

Advertisement

Air to Water Heat Pump (Split integrated DHW type)
Line
Function
850
I
Floor curing function
- Off: Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational heating + ready heating.
- Ready heating + operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends
automatically after 25 days.
55
50
45
40
35
30
25
20
0
1
5
X
Operational
heating
1
Operational heating + Heating ready for occupation
figure 50 - Diagram of the concrete slab drying programmes
I
851
Floor curing setpoint manually
(if line 850 = manual)
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed.
The concrete slab-drying programme stops automatically after running for 25 days.
I
856
Floor curing day current
857
I
Floor curing day completed
900
S
Operating mode changeover
Operating mode at end of concrete slab drying period
Cooling circuit 1
If the installation is fitted with the cooling kit (Only with the cooling kit option).
901
U
Operating mode
902
U
Comfort cooling setpoint
903
U
Reduced setpoint
908
I
Flow temp setp at OT° 25°C
909
I
Flow temp setp at OT° 35°C
I
912
Cooling limit at OT°
913
S
Lock time at end of heating / cooling
918
S
Summer comp start at OT°
919
S
Summer comp end at OT°
S
920
Summer comp setp increase
923
S
Flow temp setp min OT° 25°C
924
S
Flow temp setp min OT° 35°C
- 50 -
(figure
50)
7
1
5
10
Heating ready for occupation
Setting range
or display
15
18
Day
25
0
95 °C
0
32
0
32
None, Protection mode,
Reduced, Comfort, Automatic
Protection, Automatic, Reduced,
Comfort
17
40 °C
5 40°C
6
35 °C
6
35 °C
8
35 °C
8
100
20
50 °C
20
50 °C
1
10 °C
6
35 °C
6
35 °C
Installation and operating manual "1768 - EN"
Setting
Basic
increment
setting
" Please
comply
with
standards and instructions
of
the
manufacturer
the
building
!
A
performance of this function
is only possible with an
installation
correctly
implemented
(hydraulic,
electricity and adjustments) !
This function can be stopped
by anticipation when setting
the adjustment on "Off" .
25 °C
1 °C
1
Reduced
Protection
0,5 °C
24 °C
26 °C
0,5 °C
20 °C
0,5 °C
16 °C
24 °C
0,5 °C
1 h
1 °C
26 °C
1 °C
40 °C
1 °C
0,5 °C
18 °C
0,5 °C
18 °C
Off
the
of
good
24 h
4 °C