Fujitsu WATERSTAGE WOYG112LHT Maintenance Document page 56

Air to water heat pump
Hide thumbs Also See for WATERSTAGE WOYG112LHT:
Table of Contents

Advertisement

Air to Water Heat Pump (Split integrated DHW type)
Line
Function
Additional generator (Boiler connection)
3692
S
With DHW charging
- DHW Instantly : When DHW request, the HP and the boiler are put into operation. The HP will stop when the primary
return temperature is over 55 °C.
- DHW Substitute : If the outdoor temperature is above 2 °C, the operation of the HP when DHW request last 5 minutes
at least. The HP operating time can be extended depending on the outdoor temperature. The boiler will activate then.
3700
S
Release below outdoor temperature
3701
S
Release above outdoor temperature
3705
S
Overrun time
3720
S
Switching integral (for boiler relief)
3723
S
Locking time
Domestic hot water (DHW)
5024
S
Switching diff
S
5030
Charging time limitation
(with dynamic radiator, adjust 40 min)
5055
S
Recooling temp
5057
S
Recooling collector
S
5061
Electric immersion heater release
S
5093
With solar integration
Installation configuration
5700
I
Pre-setting
This control enables you to choose one of the 4 pre-selected installation configurations. The hydraulic layouts for the
various configurations are detailed in the section: "Installation Configurations".
- Pre-setting 1: 1 heating circuit with or without electrical back-up, with DHW tank.
- Pre-setting 2: 2 heating circuits with or without electrical back-up, with DHW tank.
- Pre-setting 3: Boiler connection and 1 heating circuit and DHW tank.
- Pre-setting 4: Boiler connection and 2 heating circuits and DHW tank.
- Pre-setting 5 and more: Not used.
5710
S
Heating circuit 1
5711
S
Cooling circuit 1
Set the parameter to "2-pipe system cooling" with the cooling kit.
5715
S
Heating circuit 2
5716
S
Cooling circuit 2
Set the parameter to "2-pipe system cooling" with the cooling kit.
If the installation consists of 2 heating circuits.
S
5731
DHW controlling element Q3
5740
S
Output el imm heater K6
5740 = Value of the DHW electrical backup - kW
5806
I
Type el imm heater flow
S
5811
Output el imm heater K25
Without electrical backup = 0 ; Single phase electrical backup (Factory setting) = 3 ; 3-phase electrical backup = 9
- 56 -
Setting range
or display
Locked, Substitute,
Complement, Instantly
-50... 50 °C
-50... 50 °C
0... 120 min
0... 500 °Cmin
1... 120 min
0
20 °C
10... 600 min
10
95 °C
Off, Summer, Always
24h / day, Release of DHW,
Programme 4 / DHW
No, Yes
1,2,3,... 9
Off, On
Off, 4-pipe system cooling,
2-pipe system cooling
Off, On
Off, 4-pipe system cooling,
2-pipe system cooling
No charging request,
Charging pump,
Diverting valve
0,1... 99 kW
1 : 3-stage, 2 : 2-stage excluding,
3 : 2-stage complementary,
4 : Modulating UX
0,1-...99
Installation and operating manual "1768 - EN"
Setting
Basic
increment
setting
Substitute
1 °C
2 °C
1 °C
--
1 min
20 min
1 °Cmin
100 °Cmin
1 min
30 min
1 °C
7 °C
90 min
10 min
1 °C
65 °C
Summer
Release of
DHW
Yes
1
1
On
Off
On
Off
Diverting
valve
2
3 :
2-stage
complementary
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents