Air to Water Heat Pump (Split integrated DHW type)
Line
Function
Inputs / outputs test
7700
I
Relay test
This consists of instructing the regulator's relays one by one and checking their outputs. This enables you to check that
the relays are working and that the cabling is correct. Check that each appliance in the installation is operating correctly.
(0) No test, (1) Everything is on STOP, (2) Relay output QX1 : heat pump CC1 (if 1 circuit ) or heat pump CC2 (if 2 circuits),
(3) Relay output QX2 : Electrical back-up (1st stage) or Boiler connection distribution valve, (4) Relay output QX3 : Electrical
back-up (2nd stage) or Boiler connection contact, (5) Relay output QX4 : DHW distribution valve, (6) Relay output QX5 :
DHW Electrical back-up, (7) Relay output QX6 , (8) Relay output QX31 : Heat circ mix valve open Y1 (or control pilot-wire),
(9) Relay output QX32 : Heat circ mix valve close Y2, (10) Relay output QX33 : heat pump CC1 if 2 circuits (mixed circuit, the less hot),
(11) Relay output QX34, (12) Relay output QX35 : Swimming pool distribution valve, (13) Relay output QX21 module 1,
(14) Relay output QX22 module 1, (15) Relay output QX23 module 1, (16) Relay output QX21 module 2, (17) Relay output QX22
module 2, (18) Relay output QX23 module 2, (19) Not used, (20) Not used, (21) Not used.
The display shows the "Key" symbol. Pressing the Info button displays "Error 368".
Warning: The component being tested is receiving electrical power throughout the test.
7710
I
Output UX1 test
7716
I
Output UX2 test
7722
I
Digital output DO2
I
7723
Heat pump D3
7724
I
Outputs test UX3 ("Inverter" command)
7725
I
Voltage value U4 (Ux3)
7804
I
Sensor temperature BX1 (HP flow temperature)
I
7805
Sensor temperature BX2 (HP return temperature)
7806
I
Sensor temperature BX3 (DHW temperature)
7807
I
Sensor temperature BX4 (Outdoor temperature)
7858
I
Input signal H3
7911
I
Input EX1 (Power shedding, EJP)
7912
I
Input EX2 (Tariffs day/night)
7913
I
Input EX3 (External fault)
State
8000
I
State heating circuit 1
8001
I
State heating circuit 2
I
8003
State DHW
8004
I
State cooling circuit 1
8006
I
State heat pump
8007
I
State solar
I
8010
State buffer
8011
I
State swimming pool
8022
I
State supplementary source
8025
I
State cooling circuit 2
Installation and operating manual "1768 - EN"
Setting range
or display
0... 100%
0... 100%
Off, On
Off, On
0... 100 %
0... 10 v
-28... 350 °C
-28... 350 °C
-28... 350 °C
-28... 350 °C
None, Closed (ooo), Open (---),
Pulse, Frequency Hz, Voltage V
0, 230 V
0, 230 V
0, 230 V
Setting
Basic
increment
setting
No test
1
--
1
--
Off
Off
--
--
--
--
--
--
None
--
--
--
--
--
--
--
--
--
--
--
--
--
- 59 -