NOTE: If powering from a 24V transformer, do not power
any other equipment with it. Otherwise, con-
ducted noise problems may result. Also, do not
ground either side of the transformer's 24V sec-
ondary.
Located at the bottom of the NPB-PWR-H module is a 2-
position power connector, and an earth ground spade lug, as
shown in Fig. 4.
Connect the supplied earth ground wire to a nearby earth
ground point. Unplug the power connector plug from the
module and make connections to it as shown.
CAUTION
Do not plug 24V power into the NPB-PWR-H
(reinsert connector plug) until all other mounting
and wiring is completed. See "Power Up and Initial
Checkout" on page 13.
Wiring NPB-PWR-UN-H input power and earth ground:
1. Remove power from the AC circuit being wired to the
NPB-PWR-H (COVER REMOVED)
DEDICATED 24VAC TRANSFORMER
NEITHER SIDE OF SECONDARY TIED
TO EARTH GROUND
24VAC
Fig. 4. NPB-PWR-H module wiring connections.
REMOVE
COVER
120 OR 240VAC
L N
50–60 HZ
SINGLE PHASE
LINE
NEUTRAL
NOTE: THE 6-PIN CONNECTOR ON THE NPB-PWR-UN-H IS NOT USED WITH
A WEB-600E SERIES CONTROLLER. THE 6-PIN CONNECTOR IS
DESIGNED FOR USE WITH OTHER CONTROLLERS OR MODULES,
AND MUST BE LEFT UNUSED.
Fig. 5. NPB-PWR-UN-H module wiring connections.
WEB-600E AND CP-600E NETWORK CONTROLLERS
EARTH
GROUND
24VDC POWER SUPPLY
(POLARITY NOT CRITICAL)
NEITHER SIDE TIED TO EARTH
OR
+
24VDC
NPB-PWR-UN-H
The NPB-PWR-UN-H module lets you power the controller
(and if installed, connected I/O modules) from AC line power,
with a universal input range from 120–240Vac. If installing IO-
16-H modules, the NPB-PWR-UN-H module mounts as the
last (end) module in the chain. (see Fig. 1).
WARNING
• A 120Vac or 240Vac circuit powers the NPB-
PWR-UN-H. Disconnect power to this circuit
before installation to prevent electrical shock or
equipment damage.
• Make all connections in accordance with
national and local electrical codes. Use copper
conductors only.
• Do not exceed the 30W capacity of NPB-PWR-
UN-H by the powered devices.
6-PIN
CONNECTOR
NOT USED
SUPPLIED EARTH
GROUNDING WIRE
EARTH
GROUND
NPB-PWR-UN-H. See the previous Warning.
2. Remove the NPB-PWR-UN-H cover.
9
SUPPLIED EARTH
GROUNDING WIRE
MCR33926
M33919
62-0433—01