WEB-600E AND CP-600E NETWORK CONTROLLERS
4-7/64
To mount on DIN rail:
1. Securely install the DIN rail with at least two screws,
near the two rail ends.
2. Position the controller on the rail, tilting to hook DIN rail
tabs over one edge of the DIN rail (Fig. 1).
3. Use a screwdriver to pry down the plastic locking clip,
and push down and in on the unit, forcing the locking
clip to snap over the other DIN rail edge.
4. Mount any accessory module (I/O module, NPB-PWR-
H) onto the DIN rail in the same manner.
62-0433—01
MOUNTING ON DIN RAIL
WEB-600E
DIN RAIL
END CLIP
WEB-600E
7-1/8 (181)
6-3/8 (162)
2-3/64 (52)
WEB-600E
(104)
10-23/64 (263)
13-37/64 (345)
16-13/16 (427)
20-3/64 (509)
23-17/64 (591)
1
IF INSTALLING IO MODULES AND USING THE NPB-PWR-H OR NPB-PWR-UN-H POWER SUPPLY
MODULE, THE POWER SUPPLY MODULE INSTALLS AT THE END OF THE CHAIN.
Fig. 1. WEB-600E controller and accessory mounting details.
REMOVING FROM DIN RAIL
NPB-PWR-H OR
NPB-PWR-UN-H
INSTALL DIN RAIL
END CLIP
(STOP CLIP) AT
DIN RAIL
BOTH ENDS OF
END CLIP
FINAL ASSEMBLY.
UP TO FOUR
IO-16-H MODULES
ARE SUPPORTED.
IO-16-H
5. Slide the accessory module along the DIN rail to con-
nect its 20-position plug into the controller.
6. Repeat this for all accessories, until all are mounted on
the DIN rail and firmly connected to each other.
7. To keep the final assembly together, secure at both
ends with DIN rail end-clips provided by the DIN rail ven-
dor. This also prevents the assembly from sliding on the
DIN rail. See Fig. 1.
4
IO-16-H
NPB-PWR-H or
NPB-PWR-UN-H
M33914