(6) WIRING
6-1 Wiring of main circuit
1.AP2G3 1 power source
terminal connect L1/R and L2/S.
2.AP2G3 3 and AP4G3 3
power source terminal connect
L1/R, L2/S and L3/T.
6-2 Wiring equipments
Select the wiring equipment and wiring size, refer to the table
below.
1. On the input power side, a molded case circuit breaker (MCCB)
to protect inverter primary wiring should be installed.
2. A leakage current breaker threshold of 200mA and above, or of
inverter use is recommended.
3. Use of input side magnetic contactor. An input MC can be used to
prevent an automatic restart after recovery from an external power
loss during remote control operation. However, do not use the MC
frequently for start/stop operation, or will lead to a reduced reliabil-
ity.
4. In general, magnetic contactors on the output of the inverter,
Should not be used for motor control. Starting a motor with the
inverter running will cause large surge currents and the inverter
overcurrent protector to trigger.
Model
Model No
137 155 175 1110 1150 1185 337 355 375 3110 3150 3185 3220 337 355 375 3110 3150 3185 3220
Capacity (KVA)
6.1 8.8 11.4 16.4 21.3 26.7 6.5
Current
(A)
16
23
Circuit Breaker
20
30
(MCCB) (A)
Electro-Magnetic
18
35
Contactor (A)
Thermal relay
15
20
RC value (A)
All manuals and user guides at all-guides.com
POWER SOURCE
AP2G3
9.2 12.6 17.6 23.3
30
43
56
70
17
24
33
50
75
100
125
20
30
50
50
65
80
93
18
35
50
28
40
55
67
15
20
28
15
APxG3-Series
L1/R
L2/S
L3/T
29
34
6.5
9.2 12.6 17.6 23.6
46
61
76
90
9
12
17
75
100
125 150
15
20
30
65
80
93
93
12
18
18
40
55
67
80
6.8
9
15
THRY
U
V
IM
W
E
AP4G3
29
34
23
31
38
45
50
50
75
75
35
48
50
50
20
28
40
40