12. DIP SWITCHES
Contact Rinnai for dip switch settings when changing PC board or setting up unit for special applications. Failure to set dip
switches to the proper position will result in damage to the unit, property damage, personal injury or death. DO NOT,
adjust dip switches unless you have written permission from Rinnai. Call 1(800)621-9419 to set-up a special training class
pertaining to dip switch functions.
The dip switches on this appliance can be adjusted to deliver water temperatures from 108°F - 180°F, only for commercial
type applications, and to check/reset low/high fire manifold pressures, and to set the unit up to operate on a different gas
type in the event the unit was converted from one gas type to another. In residential applications these switches should
never be readjusted from the factory setting. The factory default temperature setting is 120°F.
The set-up configuration for the water heater differs depending on:
Gas type
Maximum water flow selected
Temperature limiting requirements
Application type
"SW1" row of switches
1. Short or long flue
2. Fixed water temperature with or without remote.
3. To select a desired water temperature for commercial applications
4. To select a desired water temperature for commercial applications
5. To select a desired water temperature for commercial applications
6. Flow switch activated or de-activated.
7. Combustion control (Forced low fire).
8. Combustion control (Forced high fire).
Combustion control switches are used to set or check the manifold gas pressures on this appliance. When dip
switch #7 is placed in the "ON" position, it places the appliance into forced low fire. When dip switches #7 and
#8 are placed in the "ON" position, it places the unit into forced high fire. Before placing the unit into forced
low or high fire, you MUST ensure you have maximum water flow through the appliance. Open several
faucets throughout the residence before proceeding. After checking or setting manifold gas pressures, dip
switches 7 and 8 MUST be placed in the "OFF" position, to return the appliance to a normal operating
mode. Failure to place these switches to the "OFF" position will cause the unit to mal-function.
The REU-2532 series water heaters comes from the factory set to deliver a water temperature of 120 °F, the REU-2532-C
series is set to deliver 140°F. However, the commercial series will allow water temperature adjustments up to 180°F for
applications such as; hotels, car washes, laundry mats, hospitals, farms, processing plants, etc., that require water
temperatures above 120°F. Temperatures above 120 °F are not recommended due to burn hazards. Please use extreme
caution if adjusting water temperatures above 120 °F.
Explanation of "SW1" Dip Switches;
(Switch #1) Short or Long Flue Switch; at "SW1" row of switches, should be placed in the "ON" position for vent
lengths not exceeding twenty-one equivalent feet. For vent lengths over twenty-one equivalent feet this switch should be
placed in the "OFF" position.
(Switch #2) Fixed Water Temperature With or Without Remote. When this switch is set to the "OFF" position,
switches 3 – 6 can be adjusted to a pre-determined position that will not allow the remote pad to be adjusted above a
selected temperature. When set to the "ON" position and no keypad is being used, the unit can be set to deliver a set
temperature from 108, 120, 130, etc. DO NOT make adjustments without written permission from Rinnai.
REU-2532FFU Series