Friedrich Floating Air Pro Multi-Zone FPHMR42A3A Service Manual page 244

Hide thumbs Also See for Floating Air Pro Multi-Zone FPHMR42A3A:
Table of Contents

Advertisement

Field Settings (Indoor Unit Parameter Revision)
PAR AME TE R
C O D E
1
2
3
4
5
6
7
8
9
10
12
13
14
25
244
COMPONENTS TESTING
PAR AME TE R VALUE &R E PR E S E NTATIO N
PAR AME TE R
D ATA
D E SC R IPTIO N
TY PE
Self Recovery of
Integer
Power Break
Temperature Type
Integer
Temperature Display
Integer
Type
Ratio of ambient
temperature sensed
by indoor
Integer
temperature
sensor(cooling
mode)
Filter Clean
Integer
Indication
Filter Clean Time Set
Integer
Installation Height
Integer
Compensation
Cooling Temperature
Compensation
Integer
(indoor unit
temperature sensor )
Heating Temperature
Compensation
Integer
(indoor unit
temperature sensor )
Static Pressure Set
Integer
Ratio of temperature
sensed by indoor
temperature
Integer
sensor( (Heating
mode)
Temperature
Charac
Adjustment-Cooling
ter
Temperature
Charac
Adjustment-Heating
ter
Access control, fire
protection, ON/OFF
Integer
function set
R E PR E SE NTATIO N
(FUNC TIO N C O D E )
0:Cancel Self Recovery of Power
Break function ;
1:Self Recovery of Power Break ;
others:invalid
0:Centigrade Temperature ;
1:Fahrenheit Temperature ;
others:invalid
0:Default display set temperature ;
1:Default display room temperature ;
others:invalid
0~10valid ,more than 10 default is10
0:0% ;1:10% ;... ;10 :100%
0:Cancel Filter Clean prompt function ;
1:Set Filter Clean prompt function ;
others:invalid
0~32 , more than 32 default is 32*1000h
0~10m ,more than 10m default is 10.
=0,1,2 :no fan speed compensation;
=3: increase fan speed;
=4~10: increase more fan speed.
0:0°C ; 1: -0.5 °C;2: -1°C
3:-1.5 ºC; 4: -2ºC; 5: -2.5ºC;
6 : -3ºC; 7: -3.5ºC; 8: -4°C; 9: -4.5°C
10: -5°C (The wired controller displays
integer with the symbol.)
0:0°C;1:-0.5 °C;2:-1°C
3:-1.5 °C 4: -2°C; 5:-2.5 °C;
6:-3°C; 7:-3.5 °C; 8: -4°C; 9: -4.5°C
10 : -5°C ( the wired controller displays
intege r with the symbol )
1~240 ,function code=static pressure
more than the limit static pressure
default the limit static pressure ,Default
is 0( default static pressure, related to
models )
0~10valid ,more than 10 default is10
0:0% ;1:10% ;... ;10 :100%
-10~10
(Sing le Ch aracter with
symbol )
-10~10
(Sing le Ch aracter with
symbol )
=0 ,Access control, fire
protection functions are all invalid ;
=1 ,Access control function is valid ;
=2 ,fire protection function is valid ;
=3 ,Access control, fire protection are
all valid;
=4 ,ON/OFF function are all valid.
NO TE
0-entirely use
temperature
sensed b y wired
remote controller;
10- entirely use
temperature
sensed b y indoor
unit
Duct type (DC
motor )
0-entirely use
temperature
sensed b y wired
remote controller;
10- entirely use
temperature
sensed b y indoor
unit
Temperature
displayed on wired
controller
Temperature
displayed on wired
controller

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents