Air-insulated medium voltage switchgear, 12 kv/17.5 kv

Advertisement

Technical data

2
2.1
Electrical data
Rated voltage
Max. operating voltage
Rated power frequency withstand voltage
Rated lightning impulse withstand voltage
Isolation
Rated frequency
Rated current of the busbars
Rated current of the tee-offs:
• Circuit-breaker
• Switch-disconnector
Rated impulse current of
the main conductor
Rated short-circuit breaking current
of the circuit-breaker
Rated short-time current
Auxiliary voltage
1)
Special DC voltage on request.
2)
Take the short-circuit withstand capability of the instrument transformers into account separately.
For data on the individual switching devices, see ABB switchgear handbook or the instruction manual for the
switching device concerned, as listed under 7.1.
2.2
Resistance to internal arc faults
The resistance to internal arcing faults is 50 kA 1s.
Criteria 1 to 6 of PEHLA Directive No. 4 (in con-
junction with VDE 0670 part 6 and IEC 60298) are
fulfilled. Depending on the configuration of the
panels and/or the switchroom conditions (e.g. low
ceiling height), additional measures may be
necessary to ensure compliance with criterion 5.
ABB Power Distribution
kV
kV
kV
kV
Hz
A
A
kA
kA
2)
3s
kA
V
12
12
28
75
VDE/IEC List 2
50/60
... 4000
... 4000
... 1250
... 125
... 50
... 50
1)
DC
60, 110, 120; AC 110, 220
17.5
13.8
38
95
VDE/IEC List 2
50/60
... 4000
... 4000
... 1250
... 100
... 40
... 40
7