ABB ZS1 Instruction Manual page 28

Air-insulated medium voltage switchgear, 12 kv/17.5 kv

Advertisement

Section A - A
1)
50
1300
7
6
ZS1:
25kA
(80)
1075
180
180
530
11
12
1)
195
2)
360
600
2)
(100)
1050
200
Figure 5/2a: Switchgear with pressure relief via absorber into the
switchroom,
panel width: 650/800/1000 mm
16
50
6
17
870
50
11
12
Figure 5/2c: Switchgear with pressure relief to the outside,
panel width: 800/1000 mm
16
100
6
17
920
100
11
12
Figure 5/2e: Switchgear with pressure relief to the outside,
Switchgear with toroidal-core current transformers,
panel width: 1000 mm
Figure 5/2: Sections for figure 5/1
See figure 5/1 for legend
FT = panel width
1)
Minimum dimensions
2)
When minimum dimension
ABB Power Distribution
1)
FT + 700
8
14
10
13
FT + 200
Section C - C
1)
1)
1300
FT + 700
14
ZS1: > 25kA
(80)
1075
180
180
530
10
1)
195
13
2)
FT + 200
360
600
2)
(100)
1050
200
Section E - E
1)
1)
1350
FT + 700
ZS1: > 25kA
(80)
1075
180
180
530
10
1)
295
13
2)
600
460
2)
(100)
1150
200
1)
are changing the corresponding dimension
1)
50
15
6
11
12
Figure 5/2b: Switchgear without pressure relief duct,
18
8
17
6
11
12
Figure 5/2d: Switchgear with pressure relief duct and diverter,
8
14
FT + 200
Section B - B
1)
1300
FT + 700
14
(80)
1075
180
180
530
10
1)
195
13
2)
FT + 200
360
600
2)
(100)
1050
200
panel width: 650/800/1000 mm
Section D - D
FT + 700
ZS1: > 25kA
1)
50
1300
(80)
1075
180
180
530
10
1)
195
13
2)
360
600
2)
(100)
1050
200
pressure relif into the switchroom,
panel width: 800/1000 mm
2)
must be adjusted accordingly.
8
1)
8
14
FT + 200
29