Toshiba RUAGP Series Original Owner's Manual page 67

Air-cooled chiller
Table of Contents

Advertisement

Use the equipment within the operating range below.
Item
Power voltage
(Note 2)
Flow rate range
Outlet water
(Note 3)
temperature
Outdoor air
(Note 4)
temperature
In-system minimum
(Note 6)
holding water volume
In-unit holding water
volume
Note 1: The specifications shown in the table above are for one module.
Note 2: Ensure that the rated flow rate per module is within the above flow rate range. The flow rate changes automatically
according to the load fluctuation by the internal invertor pump.
Note 3: When the heat pump starts, it can be used within the following range within 1 hour only. However, during this time,
the required inlet/outlet temperature difference may not be achieved.
Cooling: Chilled water inlet 45°C or less, Cold water outlet 35°C or less
Heating: Hot water inlet 10°C or more, Hot water outlet 20°C or more
In addition, if the operating range will exceed 1 hour, install a bypass in the water piping system if necessary so that
the operation does not exceed the operating range shown in the table above.
Note 4: The warm water outlet temperature is limited by outside air temperature conditions as shown below.
60
55
50
45
40
35
30
25
20
-30 -25 -20 -15 -10
Note 5: System performance is not guaranteed between -20°C and -25°C outside air temperature.
Please be aware that system performance can be effected by external factors (for example snow drifts, the
surrounding environment etc.) even when the outside air temperature is inside the operating envelope shown above.
Note 6: When calculating holding water volume, calculate the smallest water volume for the piping flow passage, taking the
bypass channel and other factors into consideration. The holding water volumes shown in the table are values for a
designed outlet/inlet temperature differential of ΔT = 7ºC and for the values in (parentheses) a designed outlet/inlet
temperature differential of ΔT = 5ºC. Use straight line interpolation to calculate any other designed outlet/inlet
temperature differentials.
Note 7: Heat pump only.
Model
L/min
Cooling
(Note 7)
Heating
°C
Inlet/outlet temperature
difference
Cooling
°C
(Note 7)
Heating
L
L
(Powerful heating type)
- 7
-5
Outside air temperature (DB°C)
(Note1)
50HP (Powerful heating type),
50HP, 60HP
60HP (Powerful heating type)
Within ±10% of rated voltage
150 to 600
-15 to 43DB, 32WB
50HP: 717 (1075)
60HP: 860 (1290)
50HP, 60HP
70HP
50HP, 60HP
0
5
10
15
20
25
- 65 -
150 to 600
4 to 30
25 to 55
5 to 10
-15 to 52DB
-20 to 43DB, 32WB
-15 to 43DB, 32WB
36
Heat-machine
specification
(Custom order)
43
30
35
40
45
50
70HP
150 to 650
956
(1434)