8. Demand control
Demand control is possible by applying a no-voltage a-contact continuous signal to the module controller.
Demand control can applied to "Electric current: A", "Capacity: %", "Rated power ratio: %", "Power
consumption ratio: %", or "Power: kW". Demand control limits the total of all modules in the system to no
greater than the demand control value programmed in the module controller. This limit is programmable
between the following values. Refer to "6-1 Heat pump control wiring diagram" when inputting to the module
controller. It can be set in 3 stages as shown in the table below.
Digital input
Demand input 1
Demand input 2
(Note) With the initial settings of digital input items, only "Demand input 1" is valid. When using "Demand input 2",
set the digital input item to "Demand input 2" and then set the corresponding input port.
Items to which
demand control can
be applied
Electric current (A)
Capacity (L)
Rated power ratio
(R)
Power consumption
ratio (C)
Electric power (W)
Demand OFF
OFF
OFF
Unit
Limits the total of all modules in the system so that the set electric
A
current value is not exceeded.
Limits the electric current value in the system so that the capacity
%
value is not exceeded when the reference electric current value is
100%.
Limits the electric current value in the system so that the rated power
%
ratio is not exceeded when the reference electric current value is
100%.
Limits the power value in the system so that the power consumption
%
ratio is not exceeded when the power consumption at demand input
is 100%.
Limits the total power value of all modules in the system so that the
kW
set power value is not exceeded.
Demand 1
ON
OFF
Function
- 56 -
Demand 2
OFF
ON
Demand 3
ON
ON
Settable range
0 to 5000
0 to 100
0 to 100
0 to 100
0 to 5000