MC operation switching screen
Remote switch screen
MC pattern switching screen
• Use the cursor to select "Run" or "Stop" of "MC Operation".
Also, select either "Enable" or "Disable" for "System A
operation" and "System B operation". If "Disable" is selected,
the corresponding system will not operate even if "MC
operation" is set to "Run".
• If "Run" is applied, the "Run" lamp lights up. The pump starts
up first, followed by restart of the compressor and other
devices. If "Stop" is applied, the compressor and other devices
stop, and the "Run" lamp turns off. (Subsequently, the pump
continues running for at least 15 seconds.)
• When the operation setting is "Unit", operation enable/disable
for each MC operation system can be operated. The functions
that can be operated will change depending on the settings for
"External" and "Remote".
• You cannot start the MC but can force it off 1) when the
External mode is selected and the "Run/Stop" input is
specified in the I/O Settings or 2) when the Remote mode is
selected. When forced stop (Unit stop) "Enable" is selected
during "External" or "Remote" operation, the operation is
automatically switched to local operation and operation is
stopped.
• Use the cursor to select "Unit", "External" or "Remote
switching" from "Unit/Ext/Rmt".
Refer to the table below for the items and content of display
information.
Item
Unit
Operate with the MC (module controller) button.
External Operation is controlled by the external I/O signal.
Remote Operation is controlled by the GC (group controller) or Modbus.
• Use the cursor to select from "MC patterns 1 to 4" of "MC
pattern switching".
• The operation is controlled according to the setting content of
the selected "MC pattern".
• MC pattern switching is enabled when the operation settings
are "Unit" or "External" and the pattern input is not set in the
I/O settings.
• You can change the operation pattern while the heat pump is
running. However, if the system setting or operating mode
changes, the operation stops once. *1 (For the target system)
*1 Continued operation is also possible depending on the settings.
*2 The setting content of each MC pattern can be set in
"01_Unit/External operation setting" screen.