Trane SCWM Installation, Operation And Maintenance Manual page 84

Table of Contents

Advertisement

D D i i a a g g n n o o s s t t i i c c s s
Table 32. General unit alarming
External Auto/Stop (In Alarm)
Notification Class
HVAC Critical Alarm.
Local Auto/Stop (In Alarm)
Notification Class
HVAC Critical Alarm.
Discharge Air Temperature (In Fault)
Notification Class
HVAC Critical Alarm.
Diagnostic: Discharge Air Temperature Source Failure (In Alarm)
Notification Class
84
Action
Unit will shut down and be
The external auto/stop
prevented from operating
input has an open
until the sensor is in a
condition which indicates
normal state.
an emergency stop
command.
Action
Unit will shut down and be
The local auto/stop value
prevented from operating
has been commanded to
until the sensor is in a
the local stop command.
normal state.
Action
Unit will shut down and be
The temperature sensor is
prevented from running
reading either above is
until this sensor is in a
maximum value or below
normal state.
is minimum value,
resulting in a Fault
Condition after 3 point
updates.
Action
Typical Causes
Reason
Emergency stop binary
input is open.
Typical Causes
Reason
Emergency stop binary
input is open.
Typical Causes
Reason
Sensor is not wired
properly: Verify
sensor wiring to the
XM Module.
XM Module is not
communicating.
Ensure that the XM
Module is up and
talking to the UC600.
Sensor has Failed.
Verify if sensor has
any resistance on it,
should be 8-12k of
resistance on the
thermistor.
Typical Causes
Reason
Reset Required
None, alarm clears once
sensor is in a normal
state.
Reset Required
None, alarm clears once
sensor is in a normal
state.
Reset Required
None, alarm clears once
sensor is in a normal
state.
Reset Required
PKG-SVX027C-EN