M M a a i i n n t t e e n n a a n n c c e e
has completed the job, you can begin your flushing
process.
12. Though ScaleBreak-MP is a biodegradable solution,
most facilities need to conform to pH discharge
limits. ScaleBreak-MP® Neutralizer can be utilized
to safely elevate your pH to meet your discharge
limit so it can be flushed to the drain. Please follow
the instructions for this process in the ScaleBreak-
MP Neutralizer information sheet.
13. To flush your heat exchanger, turn off your
circulation pump, remove the return hose from
your recirculation system and put it in a drain.
14. Add a fresh water hose to your recirculation bucket
on your pump system and turn the pump back on.
15. Continue running clean water through the heat
exchanger for 10-15 minutes or until the return
water is running clear. This action will also flush out
your pump system.
16. As an added safeguard you can reverse your hoses
so you pump into the top and out the bottom. This
action will flush away any debris that may have
settled out the bottom of the exchanger.
17. Disconnect your hoses, close the valves you
performed your circulation through and open the
valves for the exchanger supply water.
18. Your heat exchanger can now be returned to
service.
N N o o t t e e s s : :
Follow all local regulations for discharge.
Follow all plant personal protective
equipment guidelines as determined by
your health & safety team.
ScaleBreak-MP has very minimal corrosion
rates, however, the application of
ScaleBreak -Mp may reveal pre-existing
under-deposit corrosion (UD) or
microbiologically influenced corrosion (MIC).
These types of corrosion can present
themselves in the form of pitting, pin holes
or similar types of damage.
HCl based descaling solutions are one of the
most common acid types used for descaling,
however, it is NOT recommended for use
brazed plate heat exchanger materials and
may damage the equipment, and it
therefore NOT recommended for use.
Chemical Cleaning Economizer Coil
Chemical cleaning removes scale deposits built up by
minerals in the water. For a suitable chemical solution,
consult a water treatment specialist. The condenser
water circuit is composed of copper, steel, and cast
iron.
The chemical supply house should approve or provide
all materials used in the external circulating system,
74
along with the quantity of cleaning material, duration
of cleaning time, and safety precautions necessary for
handling the cleaning agent.

Piping Components

Water Valves
W W A A R R N N I I N N G G
H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e w w / / C C a a p p a a c c i i t t o o r r s s ! !
F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r a a n n d d d d i i s s c c h h a a r r g g e e
c c a a p p a a c c i i t t o o r r s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r
s s e e r r i i o o u u s s i i n n j j u u r r y y . .
D D i i s s c c o o n n n n e e c c t t a a l l l l e e l l e e c c t t r r i i c c p p o o w w e e r r , , i i n n c c l l u u d d i i n n g g r r e e m m o o t t e e
d d i i s s c c o o n n n n e e c c t t s s a a n n d d d d i i s s c c h h a a r r g g e e a a l l l l m m o o t t o o r r s s t t a a r r t t / / r r u u n n
c c a a p p a a c c i i t t o o r r s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g . . F F o o l l l l o o w w p p r r o o p p e e r r
l l o o c c k k o o u u t t / / t t a a g g o o u u t t p p r r o o c c e e d d u u r r e e s s t t o o e e n n s s u u r r e e t t h h e e p p o o w w e e r r
c c a a n n n n o o t t b b e e i i n n a a d d v v e e r r t t e e n n t t l l y y e e n n e e r r g g i i z z e e d d . . F F o o r r v v a a r r i i a a b b l l e e
f f r r e e q q u u e e n n c c y y d d r r i i v v e e s s o o r r o o t t h h e e r r e e n n e e r r g g y y s s t t o o r r i i n n g g
c c o o m m p p o o n n e e n n t t s s p p r r o o v v i i d d e e d d b b y y T T r r a a n n e e o o r r o o t t h h e e r r s s , , r r e e f f e e r r t t o o
t t h h e e a a p p p p r r o o p p r r i i a a t t e e m m a a n n u u f f a a c c t t u u r r e e r r ' ' s s l l i i t t e e r r a a t t u u r r e e f f o o r r
a a l l l l o o w w a a b b l l e e w w a a i i t t i i n n g g p p e e r r i i o o d d s s f f o o r r d d i i s s c c h h a a r r g g e e o o f f
c c a a p p a a c c i i t t o o r r s s . . V V e e r r i i f f y y w w i i t t h h a a C C A A T T I I I I I I o o r r I I V V v v o o l l t t m m e e t t e e r r
r r a a t t e e d d p p e e r r N N F F P P A A 7 7 0 0 E E t t h h a a t t a a l l l l c c a a p p a a c c i i t t o o r r s s h h a a v v e e
d d i i s s c c h h a a r r g g e e d d . .
Water valves have a stern packing nut. If there is
evidence of water leakage at the valve stem, proceed as
follows:
1. Remove actuator motor from support plate.
2. Remove shaft coupling.
3. Torque the packing nut to 10-ft.-lbs. of torque.
4. Replace shaft coupling.
5. Replace actuator motor.
Flow Switch
Flow switches have a magnet on the vane assembly
that attracts ferrous particulate. The particulate may
build up on the magnet to the point that the vane will
wedge and not operate properly. When the flow switch
does not operate, remove and replace.
PKG-SVX027C-EN