C-TEC XFP501E/CA User Manual & Log Book page 7

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 16 & 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
LED indicators
Liquid crystal display
(General) Fire
Fire Zones
Supply Present
Test
Accessed
General Disablement
Phased Evacuation
General Fault
Power Supply Fault
System Fault
Sounder Status
Delays Running
Button controls
More Information
5
(Scroll Up)
(1)
6
(Scroll Down)
(3)
4
Accept
(2)
3
Escape
(4)
Menu
Silence Internal Sounder
Control Panel Reset
Silence / Resound Sounders Silences or resounds the system's sounders (access levels 2 & 3 only)
Investigate
Keyswitch control
USER MANUAL & LOG BOOK • Approved Document No. DFU5020000 Rev 3 • Page 7 of 24
Provides detailed info on the status of the fire alarm system, see pages 8 - 11
Flashes red when there is a fire condition on any zone and goes steady red
when the alarm is silenced. Subsequent fire conditions will restart this indicator
flashing until it is silenced again
One or more of these indicators will flash red in an alarm condition to show
which (1-16 or 1-32) zone(s) the fire is in and will go steady when silenced
Normally lit green to show that all of the panel's power supplies are
functioning correctly
Lit yellow when the panel is in walk test mode. This indicator does NOT light
for any other test condition
Lit yellow when the panel is in access level 2 or 3
Lit yellow when one or more zone, sounder, output or relay is disabled
Flashes yellow when there is a phased evacuation in process
Flashes yellow when there is a fault condition on the panel. Will always be lit
in conjunction with at least one other fault indicator
Lit yellow when the panel's power supply or Mains has failed or the panel's
standby battery is in poor condition
Lit yellow when a system error, such as a microprocessor fault, occurs AND
REMAINS LIT EVEN IF THE SYSTEM FAULT CLEARS. THIS SYSTEM FAULT LED CAN
ONLY BE CLEARED BY PRESSING THE CONTROL PANEL RESET BUTTON AT AL2/3.
Flashes yellow if there is a faulty sounder or a sounder disablement anywhere
on the system
Lit yellow when one or more output delays have been programmed by an engineer.
Flashes yellow when one or more output delays are running.
Displays additional information on any fire or fault conditions that appear
on the panel's display
Dependent on the status of the panel, these two buttons:
• scroll vertically through any fire or fault conditions that appear on the
panel's display
• scroll vertically through the panel's user menus
• manipulate date, time and disablement settings, etc.
• select Yes/No in the panel's menu options
• serve as code input buttons to access levels 2 or 3
Dependent on the status of the panel, these two buttons:
• scroll horizontally through the panel's user menus
• escape or accept options available in the panel's user menus
• serve as code input buttons to access levels 2 or 3
Provides access to the panel's user menus
Silences the panel's internal sounder
Resets the panel when the sounders are silenced (access levels 2 & 3 only)
Starts the panel's investigate timer function (access levels 2 & 3 only). Only
available if the panel's investigate function has been enabled by an engineer
Turning the keyswitch to the armed position 'I' gives the user instant access to
access level 2 (authorised user level). The key is non-removable in position 'I'.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xfp501/caXfp502/ca

Table of Contents