2.33 — Enable HTS Commercial Transfer Switch
The H-100 Control Panel can control up to four HTSs via the RS-485 communications port. The H-100 Control Panel is
shipped without the HTS control enabled. If the user has an HTS in their system, they must enable the HTS via Gen-
Link or the front panel. If the HTS is not enabled, the generator will not operate automatically with loss of utility. If the H-
100 Control Panel enables a nonexistent HTS, there will be a warning indicated.
NOTE: Non-HTS switches use the two-wire start interface and do not need enabling by H-100 Control Panel.
2.33.1— HTS Setup Using Genlink
Connect to the H-100 control panel.
Using the "Configuration" pull down, select "Transfer Switch Configuration" to display the HTS Configuration screen.
The lower left corner contains the HTS number. Use the "Prev" and "Next" buttons to select the appropriate switch
number - 1 through 4. If enabling the switch, check the "Switch Connected" check box in the middle of the screen. If
disabling the switch, uncheck the "Switch Connected" check box. The remainder of the settings on this page are
described in the HTS manual.
2.33.2— HTS Setup Using Front Panel
Press the "MENU" button.
52
H-100 Control Panel Operations Manual