This is a typical third Generator Parameters page. It graphically displays the percent of i2t thermal limit currently
attained and the percent of Current limit attained. If either limit is exceeded, an alarm will be set and the generator will
shutdown to protect the alternator. This display will then show "% Temp >Over Limit<" and/or "% Curr >Over Limit<".
On some versions, "Temp" is replaced with "i2t". GenLink can provide more information regarding actual limits
exceeded.
2.17 — Diagnostics
There are six System Diagnostic pages. They are digital inputs page, digital outputs page, two analog input pages, RS-
232 communications status page, and RS-485 communications status page.
Do the following to view the diagnostics pages:
Press the "MENU" button.
Press the
button twice and the
Press the "ENTER" button.
This is a typical first System Diagnostics page. It displays ten of the discrete inputs into the H-100 Control Panel. Inputs
to the controller are internally pulled to 5v, so to activate an input you must short it to ground. The following names are
normally assigned to these inputs:
#1 Key switch in AUTO position
#2 Key switch in MANUAL position
#3 Emergency Stop Active
#4 Remote 2-wire start Active
#5 Battery Charger Failure
Press the "ENTER" button.
H-100 Control Panel Operations Manual
button.
#6 Rupture Basin or Low Fuel Pressure
#7 Transfer Switch in Line Power Position
#8 Transfer Switch in Emergency Power Position
#9 Modem is connecting or connected
#10 Modem is present
General Information
29