2.4.4— Other Analog Options
2.4.4.1— Event Log
When set, the channel measurement is compared to the setpoint with one of the GT or LT family of options. Once the
condition is met (eg. measurement GT setpoint) the event is logged along with a date/time stamp into the volatile mem-
ory based event log. Six other parameters, that can be chosen by the customer, will also be logged. Volatile means that
when power is removed from the controller, the event log will be lost.
2.4.4.2— Analog Outputs
There are no analog outputs available for customization on an H-100 controller.
2.4.5— Analog Sensor Ratings
Typically the sensors used by the manufacturer have the following ratings:
Temperature
Pressure
2.5 — Output Functions
Output functions are flags that are set/reset by the internal program to indicate a certain status, for example "Engine
Running". The Measurement Engine allows these flags to be treated as "channels" that can be made into alarms/warn-
ings, display messages, operate real outputs and also be fed as inputs to the ILC. For example, use the "Ready To
Start" output function to operate a relay by mapping it to a physical output via GenLink, or you could feed it into the ILC
to do combinatorial logic.
See TABLE OF OUTPUT FUNCTIONS in Section 4 I/O and Connector Information.
2.5.1— Spare Analog Channels
Depending upon the particular configuration of your product, the following input channels may be available for custom
measurements:
Channel #
4
5
6
7
8
9
2.6 — Engine Management
The engine management module is very similar to that used in the manufacturer's other products. It controls engine
cranking, engine starting, engine running and engine stopping. These functions are performed to a set of "rules" that
can be customized via parameters from GenLink. In turn, the module needs to know certain things about the engine
which it expects to be programmed in from GenLink.
H-100 Control Panel Operations Manual
35 - 300° F
0 - 150 psi
Normal Function
Coolant Level
Fuel Level
Ignition Module Alarm
Throttle Position
Oxygen Sensor 0-1 VDC
Battery Charge Current 0-5 VDC
General Information