7.6.1— GFI enable
The enable check box will be grayed out for the following conditions:
Insufficient Security Level.
Firmware version is not 3.7D or later.
Unit is not a 3-Phase Unit.
If enable check box is not grayed out and is checked, the GFI Screen will be similar to Figure 7-1. Otherwise, all edit-
able fields will be grayed out.
7.6.2— GFI Screen's System Generated Fields
The following fields are system generated:
7.6.2.1— Generator Rated Current (RMS Amps)
Derived from system's Voltage and kW parameter settings.
Dependent on Unit Configuration.
7.6.2.2— Generator Average Current (RMS Amps)
Derived from Average Current of all Phases while unit is running.
Dependent on Unit Configuration and load conditions.
7.6.2.3— Generator Gnd + Neutral Current (RMS Amps)
Derived from Unit's Ground Current and Neutral Current while running.
Dependent on Unit Configuration and load conditions.
7.6.3— GFI Field Editable Parameters
The following fields are field editable by field service technician, site engineer, or similar:
7.6.3.1— Gnd + Neutral Current Threshold (RMS Amps)
FACTORY DEFAULT VALUE = 100% of Generator Rated Current (Unit Configuration Dependent)
This can be changed in field to meet site engineer's recommendation or similar authority.
7.6.3.2— Gnd + Neutral Current Hysteresis (RMS Amps)
FACTORY DEFAULT VALUE = 1/16 * "Gnd + Neutral Current Threshold" Value
This can be changed in field to meet site engineer's recommendation or similar authority.
7.6.3.3— Gnd + Neutral Fault Delay(s)
FACTORY DEFAULT VALUE = 1 Second
This can be changed in field to meet site engineer's recommendation or similar authority.
7.6.3.4— Analog Input Channel Assignment (chan_ID)
FACTORY DEFAULT VALUE = "NULL"
Please see guidelines under the "GENLINK HELP SCREEN INFORMATION" Section before changing this
value.
7.6.3.5— Digital Output Function Assignment (chan_ID)
FACTORY DEFAULT VALUE = "192 (DOF_118)" for H-Panel Controls (as shown in Figure 7-1) or "191
(DOF_117)" for G-Panel Controls
This output is used to indicate the Ground Fault (GFI).
H-100 Control Panel Operations Manual
Ground Fault Indication
77