Troubleshooting
Fault codes
(cont.)
Fault code dis-
System characteristics
played
96
Burner blocked
98
Control mode
99
Control mode
9A
No solar DHW heating
9b
Control mode
9C
No solar DHW heating
9E
Control mode
9F
Control mode
A3
Burner blocked.
A7
Control mode as per deliv-
ered condition
A9
Burner blocked.
B0
Burner in a fault state
b1
Control mode as per deliv-
ered condition
b5
Control mode as per deliv-
ered condition
b7
Burner blocked
B8
Burner in a fault state
bF
Control mode
C1
Control mode
C2
Control mode
C3
Control mode
64
Cause
CO limiter sensor fault
Lead break, temperature
sensor
/
Lead break, temperature
sensor
Lead break, collector tem-
perature sensor
Lead break, collector re-
turn temperature sensor
Lead break, cylinder tem-
perature sensor
No or inadequate flow rate
in collector circuit, or tem-
perature limiter has re-
sponded.
Solar control module or
Vitosolic fault
Flue gas temperature sen-
sor incorrectly positioned.
Programming unit faulty
Internal circulation pump
blocked
Short circuit, flue gas tem-
perature sensor
Communication error, pro-
gramming unit
Internal fault
Boiler coding card fault
Lead break, flue gas tem-
perature sensor
Incorrect LON communi-
cation module
Communication error, EA1
extension
Communication error, so-
lar control module or
Vitosolic
Communication error,
AM1 extension
Measures
Replace the CO limiter.
If the system is to be temporarily
operated without a CO limiter:
Disconnect plug X21 from the
control unit.
Set parameter 49:0.
Check sensor
on solar control
/
module.
Check sensor
on solar control
module.
Check temperature sensor
solar control module or sensor on
the Vitosolic.
Check temperature sensor at ter-
minal S3 on the Vitosolic 100.
Check temperature sensor
solar control module or sensor on
the Vitosolic.
Check solar circuit pump and solar
circuit. Acknowledge fault mes-
sage.
Replace solar control module or
Vitosolic
Fit flue gas temperature sensor
correctly (see page 76).
Replace the programming unit.
Check circulation pump.
Check flue gas temperature sensor
and connecting lead.
Check connections; replace pro-
gramming unit if necessary.
Replace control unit.
Plug in boiler coding card or re-
place if faulty.
Check flue gas temperature sensor
and connecting lead.
LON communication module.
Check connections.
Check solar control module or
Vitosolic
Check connections.
on
&
on
%