Coding level 2
(cont.)
Coding in the delivered condition
6E:50
No display correction for outside
temperature.
76:0
Never adjust
7E:0
One boiler connected to the flue
system (single connection)
80:6
A fault message is issued if a fault
is present for at least 30 s.
81:1
Automatic summer/wintertime
changeover
82:0
Never adjust
88:0
Temperature displayed in °C (Cel-
sius)
8A:175
Never adjust
8F:0
All controls active
90:128
Time constant for calculating the
adjusted outside temperature
21.3 h
93:...
Never adjust
94:0
Without OpenTherm extension
95:0
Without Vitocom 100 communica-
tion interface, type GSM
96:...
Minimum burner output dependent
on the specifications of the boiler
coding card
99:0
Never adjust
Possible change
54:2
With Vitosolic 200 (automatic recog-
nition).
54:3
No function
54:4
With solar control module SM1 with
auxiliary function, e.g. central heat-
ing backup (automatic recognition)
6E:0
Display correction
to
6E:49
6E:51
Display correction +0.1 K to +5 K
to
6E:100
7E:1
Several boilers connected to one
shared flue system (multiple connec-
tions)
80:0
Immediate fault message
80:2
Minimum fault duration until fault
to
message occurs, adjustable from
80:199
10 s to 995 s; 1 step
81:0
Manual summer/wintertime change-
over
81:2
Use of the radio clock receiver (au-
tomatic recognition).
81:3
With LON communication module:
Control unit receives the time.
88:1
Temperature displayed in °F (Fah-
renheit)
8F:1
All controls disabled
8F:2
Only standard settings can be con-
trolled
90:1
Subject to the set value, the flow
to
temperature is adjusted quickly (low
90:199
values) or slowly (high values) when
the outside temperature changes;
1 step
94:1
With OpenTherm extension (auto-
matic recognition)
95:1
With Vitocom 100 communication in-
terface, type GSM (automatic recog-
nition)
96:...
Minimum burner output adjustable
to
from ... to 100 % of the rated heating
96:100
output