Precautions on electrical wiring work 
 
Fix cables so that cables do not make contact with the pipes (especially on the high 
pressure side). 
Secure the electrical wiring with cable ties as shown in figure so that it does not 
come in contact with the piping, particularly on the high‐pressure side. 
Make sure no external pressure is applied to the terminal connectors.
When installing the ground fault circuit interrupter make sure that it is compatible 
with  the  inverter  (resistant  to  high  frequency  electrical  noise)  to  avoid 
unnecessary opening of the ground fault circuit interrupter. 
 
 
 
The  ground  fault  circuit  interrupter  must  be  a  high‐  speed  type  breaker  of  30  mA 
 
(<0.1s) 
 
 
This unit is equipped with an inverter. Installing a phase advancing capacitor not 
only  will  reduce  the  power  factor  improvement  effect,  but  also  may  cause 
abnormal heating of the capacitor due to high‐frequency waves. Never install a 
phase advancing capacitor as it could lead to an accident.  
 
Precautions on wiring of power supply 
 
Use  a  round  crimp‐style  terminal  for  connection  to  the  power  supply  terminal 
board. In case it cannot be used due to unavoidable reasons, be sure to observe 
the following instructions. 
 
-
Do  not  connect  different  gauge  wires  to  the  same  power  supply  terminal. 
(Loose connections may cause overheating.) 
-
When  connecting  wires  of  the  same  gauge,  connect  them  according  to  the 
figure below. 
 
Use the correct screwdriver to tighten the terminal screws. Small screwdrivers can 
damage the screw head and prevent appropriate tightening. 
Over‐tightening the terminal screws can damage the screws. 
Attach a ground fault circuit interrupter and fuse to the power supply line. 
In  wiring,  make  certain  that  prescribed  wires  are  used,  carry  out  complete 
connections, and fix the wires so that outside force cannot affect the terminals 
 
 
 NOTE 
 