Ariston NEMUS CONSOLE R32 User And Installation Manual page 41

Table of Contents

Advertisement

Available languages

Available languages

STANDARD
Do not install the air conditioning unit near sources of heat or flammable
material.
Do not install the air conditioning unit near heat sources, flammable ma-
terial or in an area with ignition sources in continuous operation (e.g.
naked flames, gas appliances in operation or electrical stoves in opera-
tion).
Do not install the air conditioning unit in areas at risk of flammable gas
leaks.
Once installation is complete, check there are no gas leaks in the work
area. In the event of a refrigerant leak, ventilate the area immediately.
During installation or transfer of the air conditioning unit, make sure the
refrigerant circuit has been bled to ensure no air is present. Only use
the specified refrigerant (R32).
NOTE:
The unit must be installed, commissioned and stored in a room of area at least X m² (see Max Refrigerant Charge
table). The appliance may not be installed in an unventilated room smaller than X m² (see Min Room Area table).
h
Values depend on the installation type (eg:0,6 x floor standing installations.)
0
Refer to IEC 60335-2-40:2013 regulation.
MAX Refrigerant Charge (kg)
LFL (kg/m3)
R32
0.306
MIN Room Area (m2)
LFL (kg/m3)
R32
0.306
Height h
(m)
0
0.6
1.0
1.8
2.2
Height h
(m)
0
0.6
1.0
1.8
2.2
RISK
Personal injury, fire hazard.
Personal injury, fire hazard.
Personal injury, fire hazard.
Personal injury, fire hazard.
Damage to the appliance, injury.
Floor Area (m2)
4
7
10
0.68
0.90
1.08
1.14
1.51
1.80
2.05
2.71
3.24
2.50
3.31
3.96
Total refrigerant charge (kg)
1.224
1.836
2.448
29
51
10
19
3
6
2
4
15
20
30
1.32
1.53
1.87
2.20
2.54
3.12
3.97
4.58
5.61
4.85
5.60
6.86
3.672
4.896
6.12
116
206
321
42
74
116
13
23
36
9
15
24
/ 41
GB
50
2.41
4.02
7.24
8.85
7.956
543
196
60
40