Connection to evaluation devices

General

Independent circuit

Please note:
}
When connected to the PSEN ix2 F8 code, the sequence of the sensors must be main-
tained.
Operating Manual PSEN ix2 F8 code
1003867-EN-02
Device
Function
Fieldbus
Status of signal output/diagnostic output of
module
PSEN 4
Status of signal input/diagnostic input of
PSEN 4
Status of signal output/diagnostic output of
PSEN 3
Status of signal input/diagnostic input of
PSEN 3
Status of signal output/diagnostic output of
PSEN 2
Status of signal input/diagnostic input of
PSEN 2
Status of signal output/diagnostic output of
PSEN 1
Status of signal input/diagnostic input of
PSEN 1
NOTICE
Each time the cabling is changed during commissioning, trigger the safety
function of each sensor in the safety chain and check that the safety outputs
on the evaluation device react correctly.
PSEN 1: Terminal block X1, terminals 11-18
PSEN 2: Terminal block X1, terminals 21-28
PSEN 3: Terminal block X2, terminals 11-18
PSEN 4: Terminal block X2, terminals 21-28
PSEN 5: Terminal block X3, terminals 11-18
PSEN 6: Terminal block X3, terminals 21-28
PSEN 7: Terminal block X4, terminals 11-18
PSEN 8: Terminal block X4, terminals 21-28
Cable colour