PSEN ix2 F8 code
Connecting fewer than eight sensors
}
If fewer than eight sensors are connected to a PSEN ix2 F8 code the free sensor ter-
minals on terminal blocks X1 to X4 must be bridged.
Fig.: Terminal block X1 with three bridges for an unconnected sensor
Connection without fieldbus module
}
If the PSEN ix2 F8 code will not be connected to a fieldbus module, the bridges that are
inserted on terminals X5 Y2 ‑ Y7 and X6 Y2 ‑ Y7 when the PSEN ix2 F8 code is de-
livered must all be removed. The respective states of the sensors' signal input/dia-
gnostic input Y1 and signal output/diagnostic output Y32 are output at these terminals.
To evaluate the data, the relevant control system must be connected to the terminals
(see diagram).
Operating Manual PSEN ix2 F8 code
1003867-EN-02
Terminal blocks X1 to X4
Bridges between terminals 11 and 17, 12 and 18 and 15 and 16.
Bridges between terminals 21 and 27, 22 and 28 and 25 and 26.
The terminals on terminal blocks X1 to X4 must be bridged for each unconnected
sensor (see diagram).
X1
21 22
Terminal blocks X5 and X6, terminals Y1, Y3, Y5, Y7 for the sensors' signal output/
diagnostic output Y32
Terminal blocks X5 and X6, terminals Y2, Y4, Y6, Y8 for the sensors' signal input/
diagnostic input Y1
23
24
25
26
27
28