Codes
Code 2
(cont.)
Coding in the delivered condition
A6:36
Extended economy mode not ac-
tive
A7:0
Without mixer economy function
(only for heating circuits with mix-
er)
A9:7
With pump idle time: Heating cir-
cuit pump "OFF" if set value is
modified by changing the operating
mode or changing the set room
temperature
b0:0
With remote control: Heating
mode/reduced mode: Weather-
compensated (change the code
only for the heating circuit with
mixer)
b2:8
With remote control and for the
heating circuit, operation with room
temperature hook-up must be pro-
grammed: Room influence factor 8
(only change the code for the heat-
ing circuit with mixer)
b5:0
With remote control: No room tem-
perature-dependent heating circuit
pump logic function (change code
only for heating circuit with mixer)
Parameter address
With heating circuit pump logic function:
b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
74
> RT
+ 5 K
actual
set
> RT
+ 4 K
actual
set
> RT
+ 3 K
actual
set
> RT
+ 2 K
actual
set
> RT
+ 1 K
actual
set
> RT
actual
set
Possible change
A6:5
Extended economy mode active:
to
The burner and heating circuit pump
A6:35
are switched off at a variable value,
adjustable from 5 to 35 °C plus 1 °C.
Mixer is being closed. The basis for
this is the adjusted outside tempera-
ture. This is derived from the actual
outside temperature and a time con-
stant that takes account of the way
an average building cools down.
A7:1
With mixer economy function (exten-
ded heating circuit pump logic):
Heating circuit pump also "OFF":
If the mixer has been trying to
close for more than 20 min.
Heating circuit pump "ON":
If the mixer changes to control
function.
If there is a risk of frost
A9:0
Without pump idle time
A9:1
With pump idle time, adjustable from
to
1 to 15
A9:15
b0:1
Heating mode: Weather-compensa-
ted
Reduced mode: With room tempera-
ture hook-up
b0:2
Heating mode: With room tempera-
ture hook-up
Reduced mode: Weather-compen-
sated
b0:3
Heating mode/reduced mode: With
room temperature hook-up
b2:0
Without room influence
b2:1
Room influence factor adjustable
to
from 1 to 64
b2:64
b5:1
For heating circuit pump logic func-
to
tion, see the following table:
b5:8
Heating circuit pump "ON"
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
+ 4 K
+ 3 K
+ 2 K
+ 1 K
1 K