Viessmann Vitoladens 300-C Installation And Service Instructions Manual page 61

Oil condensing boiler with integral boiler control unit
Hide thumbs Also See for Vitoladens 300-C:
Table of Contents

Advertisement

Code 1
(cont.)
Parameter address A5:...
1
2
3
4
5
6
7
to
15
Coding in the delivered condition
Extended economy function adjusted outside temperature
A6:36
Extended economy mode not ac-
tive
Extended economy function mixer
A7:0
Without mixer economy function
(only for heating circuits with mix-
er)
Pump idle time, transition reduced mode
A9:7
With pump idle time: Heating cir-
cuit pump "OFF" if set value is
modified by changing the operating
mode or changing the set room
temperature
Weather-compensated/room temperature hook-up
b0:0
With remote control: Heating
mode/reduced mode: Weather-
compensated (change the code
only for the heating circuit with
mixer)
With heating circuit pump logic function: Heating circuit pump "OFF"
OT > RT
+ 5 K
set
OT > RT
+ 4 K
set
OT > RT
+ 3 K
set
OT > RT
+ 2 K
set
OT > RT
+ 1 K
set
OT > RT
set
OT > RT
1 K
set
OT > RT
9 K
set
Possible change
A6:5
to
A6:35
A7:1
A9:0
A9:1
to
A9:15
b0:1
b0:2
b0:3
Extended economy mode active:
The burner and heating circuit pump
are switched off and the mixer will
be closed at a variable value, adjust-
able between 5 and 35 °C plus 1 °C.
The basis for this is the adjusted
outside temperature. This is derived
from the actual outside temperature
and a time constant that takes ac-
count of the way an average building
cools down.
With mixer economy function (exten-
ded heating circuit pump logic):
Heating circuit pump also "OFF":
If the mixer has been trying to
close for more than 20 min.
Heating circuit pump "ON":
If the mixer changes to control
function
If there is a risk of frost
Without pump idle time
With pump idle time, adjustable from
1 to 15
Heating mode: Weather-compensa-
ted
Reduced mode: With room tempera-
ture hook-up
Heating mode: With room tempera-
ture hook-up
Reduced mode: Weather-compen-
sated
Heating mode/reduced mode: With
room temperature hook-up
Codes
61

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bc3B23B23pC33C43C53 ... Show all