Checking The Activated Carbon Filter (Accessories); Checking The Expansion Vessel And System Pressure; Adjusting The Standard Burner Settings - Viessmann Vitoladens 300-C Installation And Service Instructions Manual

Oil condensing boiler with integral boiler control unit
Hide thumbs Also See for Vitoladens 300-C:
Table of Contents

Advertisement

Checking the activated carbon filter (accessories)

Note
Observe the manufacturer's documentation included
for the activated carbon filter.

Checking the expansion vessel and system pressure

Adjusting the standard burner settings

Note
To be able to adjust the burner, there must be a heat
demand and heat transfer must also be assured.
Standard values for burner adjustment
Note
Check that the service instructions are applicable to
the relevant burner. See applicability information on
the last page and serial no. on the boiler type plate.
Fig. 46
Flue gas test port
A
Rated heating output
at T
/T
50/30 °C
F
R
at T
/T
80/60 °C
F
R
Burner stage
Rated heat input
Oil burner nozzle
Make: Danfoss
Oil pressure approx.
Min.
Max.
Max. permiss. vacuum in
the oil line
Oil throughput approx.
kW
12.9/19.3
kW
12/18
1
kW
12.5
Type
80° H LE
Gph
0.40
bar
8
MPa
0.8
bar
10.5
MPa
1.05
bar
0.35
kPa
35
kg/h
1.05
l/h
1.24
Commissioning, inspection, maintenance
16.1/23.6
15/22
2
1
18.7
15.6
22.9
80° H LE
0.50
16.5
10
1.65
1.0
20
13
2.0
1.3
0.35
0.35
0.35
35
35
1.58
1.53
1.92
1.86
1.80
2.26
19.3/28.9
18/27
2
1
18.7
28.1
80° H LE
0.50
18
8.5
1.8
0.85
1.7
22
13.5
2.2
1.35
2.5
0.35
0.35
35
35
1.58
2.37
1.86
2.78
2
17
25
35
49

Hide quick links: