Standard values for water quality

Advantages of complying with the guidelines
Prolonged boiler service life
Reduced repair costs
Advantages of using chemical water treatment
The specified standard values and water conditions
are observed
No additional corrosion protection is required
If the system is designed as a hot water heating
system sealed against corrosion and
If all the other instructions stated in chapter "Stand-
ard values for water quality" are complied with

Flow temperatures

100 °C (VDI 2035 Part 1-2)
Recommendations
Prevent scale deposits (calcium carbonate) from
forming on the heating surfaces.
Pay particular attention to the standard values speci-
fied in VDI Guideline 2035 Part 1 "Prevention of
damage in water heating installations – Scale forma-
tion in domestic hot water supply installations and
water heating installations".
Conditions of applicability
Fill and top-up water consumed by the system during
its service life: Max. 3 times its capacity
Specific system volume: < 20 l/kW heating output. In
the case of multi boiler systems: The output of the
smallest steam boiler or hot water boiler applies here
All measures to prevent corrosion on the water side
in accordance with VDI 2035 Part 2 have been com-
plied with
Standard values (extract)
Total heating output
Total alkaline earths
Total hardness
Tab. 1
Fill and top-up water
Soften the water:
If the total of alkaline earths in the fill and top-up
water exceeds the standard value
If larger fill and top-up water volumes are expected
Log the water volumes:
Install a water meter
Enter the volume of water filled and the water hard-
ness in the boiler system operator's log
Reduction of water consumption:
Install shut-off valves in each section of the system.
This enables the heating water to be drained just
from the affected section when work is required on
the system.
kW
600
>
3
< 0.02
mol/m
°dH
< 0.11
Recommendation
Use a chemical water treatment system in the boiler
system.
Request a quotation from Viessmann (for contact
details, see page 33).
Note
Observation of the following requirements is a neces-
sary condition for safeguarding your warranty rights.
The warranty excludes damage caused by scaling or
failure to adhere to water quality conditions.
Operating information
Start the system in stages:
Begin with the boiler with the smallest output
Prevent localised limescale deposits on the heating
surfaces by setting a high heating water flow velocity
When carrying out work on the system, only drain
the affected sections of the system
Only fill the heating system with treated water:
Occasions when this will be necessary:
Commissioning
Recommissioning
After repairs or system expansion
Filling with top-up water
Check filters, dirt traps and other blow-down or sepa-
rating facilities in the heating water circuit for depos-
its; clean them and check they are working correctly:
How often:
After commissioning and reinstallation: At shorter
intervals
Depending on the water treatment applied, e.g.
water softening: As required
Limescale deposits
Production
Limescale deposits shorten the service life of the
boiler. They form when the specified preventive meas-
ures have not been implemented correctly.
Preventive action:
Observe VDI Guideline 2035
Observe the information in these instructions
Remedies:
Remove deposits immediately
Restore operational viability of the boiler system
Check the boiler system for damage before recom-
missioning
Ensure that excessive limescale deposits (scaling)
cannot recur
Rectify incorrect operating parameters
Water quality
9