Standard values for water quality
Protecting the heating water from oxygen ingress
Prevent continuous oxygen ingress and the entry of
airborne oxygen into the system during operation.
Apply technical rules, specifically VDI Guideline
2035-2.
Ensure that the heating system is designed correctly
(dimensions, system pressure).
Operate the heating system in line with regulations.
Equip sealed unvented systems with a diaphragm
expansion vessel, for example.
Recommendation for diaphragm expansion vessel
Check the pre-charge pressure during the annual serv-
ice at the latest.
Pressure maintaining systems and corrosion
"General engineering information" chapter in the
technical guide
Operate the system with positive pressure
In the entire boiler system
On the pump suction side
In every system operating state
(cont.)
Additional protection against oxygen ingress
Add an oxygen binder (excess of 5 - 10 mg
Na
SO
/l).
2
3
Adjust the pH value of the heating water to 8.2 - 9.5.
Use of aluminium components
Bear in mind that different conditions may apply.
Corrosion protection with chemicals:
Obtain a safety declaration from the chemical manu-
facturer regarding the interaction of the chemicals with
the materials used in the steam boiler, the hot water
boiler and the other components of the heating sys-
tem.
Recommendation
Consult the relevant contractor regarding water treat-
ment.
Detailed information
VDI Guideline 2035-2 and EN 14868
Water quality
11