Download Print this page

Siemens LME39 Series Quick Start Manual page 7

Gas burner controls
Hide thumbs Also See for LME39 Series:

Advertisement

Type summary (other types of burner controls on request)
Flame detector
Product no.
Burner controls for 2-stage burners with actuator control and communication
Ionization probe (ION)
LME39.100A1
or flame detector
3)
QRA...
with
LME39.100A2
AGQ3...A27
min.
Setting range
Max.
Increment
(s)
Burner controls for atmospheric, 2-stage burners without actuator control with communication
Ionization probe (ION)
LME39.400A1
or flame detector
3)
QRA...
with
LME39.400A2
AGQ3...A27
min.
Setting range
Max.
Increment
(s)
Note on parameterization:
Use the AZL2... or ACS410 to always set the exact value of the required time (multiples of increments of 0.147
seconds or 0.294 seconds).
When parameterizing minimum or maximum times, the possibility of a ±7% tolerance must be taken into con-
sideration.
For minimum values: The value to be parameterized must be at least 7% greater.
For maximum values: The value to be parameterized must be at least 7% smaller.
Example:
Calculation:
Value to be parameterized:
Example:
Special case here:
Calculation:
Value t3n to be
parameterized:
tw
Waiting time
Legend
TSA
Safety time
t1
Prepurge time
t1´
Purge time
t3
Preignition time
t3n
Postignition time
1)
Maximum running time available for actuator «SA». The actuator's running time must be shorter
2)
Repetition (maximum number of startups per controlled start)
3)
Only AC 230 V
Building Technologies
HVAC Products
The product nos. given below apply to the LME39... burner control without plug-in base
and without flame detector. For ordering information on plug-in bases and other accesso-
ries, refer to «Ordering».
tw
TSA
Main
voltage
max.
max.
s
s
(3)
AC 120 V
2.5
t3n + 0.7
(3)
AC 230 V
2.5
t3n + 0.7
---
---
0.7
---
---
4.7
---
---
0.147
(5)
AC 120 V
2.5
t3n + 0.7
(5)
AC 230 V
2.5
t3n + 0.7
---
---
0.7
---
---
4.7
---
---
0.147
t1min shall be set to 30 s
30 s + 7% = 32.1 s
Must be equal to or greater than the calculated value
(e.g. 32.34 s)
TSAmax. shall be set to 5 s
TSA is set directly via the change of t3n using the following formula:
t3n = TSA – 0.7 s
5 s – 7% = 4.65 s
t3n = 4.65 s – 0.7 s = 3.95 s
Must be equal to or smaller than the calculated value (e.g. 3.822 s)
t1
t1´
t3n
t3
(P225)
(P256)
(P257)
(P226)
ap-
approx.
min.
min.
prox.
s
s
s
s
30
---
3
2.3
30
---
3
2.3
0
---
1
0
75
---
37.5
4
0.294
---
0.147
0.147
---
14.5
1.7
4
---
14.5
1.7
4
---
0
1
0
---
75
37.5
4.2
---
0.294
0.147
0.147
t4
Interval between ignition «Off» and «BV2»
t8
Postpurge time
t10
Specified time for air pressure signal
t11
Programmed opening time for actuator «SA»
t12
Programmed closing time for actuator «SA»
t22
2nd safety time
t8
t10
t11
t4
(P234)
(P224)
(P259)
(P230)
approx.
min.
max.
min.
s
1)
s
s
s
10
0
65
30
10
0
65
30
1
0
---
0
75
240
---
75
0.294
5
---
0.294
9
0
---
---
9
0
---
---
1
0
---
---
75
1237
---
---
0.294
5
---
---
t12
t22
(P260)
ap-
2)
min.
prox.
1)
s
s
30
---
1
30
---
1
0
---
1
75
---
4
0.294
---
1
---
5
1
---
5
1
---
0
0
---
8
4
---
0.147 1
7/17
CC1N7106en
20.02.2008