Siemens LME39 Series Quick Start Manual page 6

Gas burner controls
Hide thumbs Also See for LME39 Series:

Advertisement

Standards and certificates
Disposal notes
Mechanical design
LME39...
Indication and
diagnostics
Display and
communication
Time parameters
6/17
Building Technologies
HVAC Products
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Directive for gas-fired appliances
ISO 9001: 2000
ISO 14001: 2004
Cert. 00739
Cert. 38233
Identification code to EN 298
LME39.100...
LME39.400...
The unit contains electrical and electronic components and must not be disposed of to-
gether with domestic waste.
Local and currently valid legislation must be observed.
The housing is made of impact-proof, heat-resistant and flame-retarding plastic. It is of
plug-in design and engages audibly in the base
Burner controls LME39... and plug-in base AGK11.6 are silver-grey (RAL7001)
The housing accommodates the
- microcontroller for the control sequence and the control relays for load control
- electronic flame signal amplifier (ionization)
- lockout reset button with its integrated 3-color signal lamp (LED) for operational
status and fault status messages and the socket for connecting the OCI400 inter-
face adapter
The AZL2... display and operating unit is for direct connection to the burner control. All
safety-related digital inputs and outputs of the system are monitored by the contact
feedback network. Operation and parameterization of the LME39... is accomplished
with the AZL2... or via the OCI410... / ACS410
Unlimited burner capacity (thermal output on startup ≤120 kW)
3 repetitions in the event of loss of flame during operation (can be parameterized)
Multicolor indication of operational status and fault status messages
Forwarding of operational status messages, fault status messages and full service
information via additional OCI400 / OCI410... interface adapter and Windows ACS410
PC software
RJ11 jack for connection of the AZL2... display and operating unit or the OCI410... inter-
face adapter for communication and parameterization via Windows ACS410 PC tool.
The most important time parameters for the program:
Prepurge time (t1)
Preignition time (t3)
Postignition time (t3n)
Interval (t4)
Postpurge time 1 (t8-1)
Opening time for actuators (t11)
Closing time for actuators (t12)
Both the prepurge time and the safety times are safety-related and can be changed by the
OEM with the help of the display and operating unit.
F T C L B N
A B C L B N
2004/108/EC
90/396/EEC
CC1N7106en
20.02.2008