Programming Menu; General Notes; Block Diagram For Entering The Menu - Riello BS2D Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

Available languages

Available languages

5.14 Programming menu

5.14.1 General notes

The programming menu can be accessed via the integrated reset
button, or by remote reset during OPERATION and in STAND-
BY.
If in page menu the reset or remote reset button is not pressed
within 10 seconds the page will be automatically be exited and
there will be a green led blinking for the time set.

5.14.2 Block diagram for entering the menu

BURNER STATE
TYPE OF
SWITCHING OFF
FUNCTION
TEST
BUTTON
TIME
RELEASE
5 SEC.
NUMBER
2 RED
BLINKS
AUTOMATIC
OUTLET
OUTLET
S9640
Button
Function
release time
Switching off
5s ≤ t < 10s
test
Post-purging/
10s ≤ t < 15s
Continuous
purging
Intermittent
20s ≤ t < 25s
operation
Opening delay
25s ≤ t < 30s
2nd stage
Long
30s ≤ t < 35s
pre-purging
Displaying
35s ≤ t < 40s
lockout logs
Parameter
40s ≤ t < 45s
reset
programming
menu
OPERATION (WITH FLAME) AND STAND-BY
POST-PURGING/
INTERMITTENT
CONTINUOUS
OPERATION
PURGING
10 SEC.
20 SEC.
1 GREEN
3 GREEN
10 SEC. AFTER
10 SEC. AFTER
RELEASE
RELEASE
No. of blinks of
No. of pressings
the led per
of the reset button
menu page
2 blinks
/ none
RED
1 GREEN blink
1 = 1 minute
2 = 2 minutes
3 = 3 minutes
4 = 4 minutes
5 = 5 minutes
6 = 6 minutes
7 = continuous purging
8 = 0 m (deactivated)
(default)
3 blinks
1 = 1 hour
GREEN
2 = 24 hours (default)
4 blinks
1 = 8 sec (default)
GREEN
2 = 20 sec
3 = 35 sec
5 blinks
1 = activated
GREEN
2 = deactivated
(default)
6 blinks
1 = last lockout
GREEN
2 = 9th lockout
3 = 8th lockout
4 = 7th lockout
5 = 6th lockout
6 = 5th lockout
7 = 4th lockout
8 = 3rd lockout
9 = 2nd lockout
10 = less recent lockout
7 blinks
1 = reset of the
GREEN
lockout logs
2 = reset of the no. of
lockouts
3 = reset of hours of
operation
4 = reset of the no. of
heat requests
5 = restoration of
default values of the
menu parameters
Installation
If the number of presses on the reset or remote reset button ex-
ceeds the maximum allowable, the value that stays in memory
will be the maximum one.
If the reset or remote reset button is pressed for more than 60
seconds, a reset button error will be displayed.
OPENING
LONG PRE-PURG-
DELAY
2nd STAGE
25 SEC.
4 GREEN
10 SEC. AFTER
10 SEC. AFTER
RELEASE
No. of blinks of
the LED (green)
/ none
1 blink
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
1 blink
2 blinks
1 blink
2 blinks
3 blinks
1 blink
2 blinks
Displaying the
type of lockout
according to
Tab. M
/
31
GB
DISPLAYING
ING
LOCKOUT
LOGS
30 SEC.
35 SEC.
5 GREEN
6 GREEN
10 SEC. AFTER
RELEASE
RELEASE
Quitting the menu
Automatic, at the
end of the blink
10 sec. after the release of the
button
10 sec. after the release of the
button
10 sec. after the release of the
button
10 sec. after the release of the
button
10 sec after the release of the
button (if at level 1).
When at level 2, 10 sec after the
display of the type of lockout or
else pressing the button again
before 10 sec you return to level
1 from where, 10 seconds after
nothing has been done to the
buttons, you exit the menu
10 sec. after the release of the
button
PROGRAMMING
MENU PARAME-
TER RESET
40 SEC.
7 GREEN
10 SEC. AFTER
RELEASE
Fig. 23
Tab. P
20135737

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Bs1dBs3dBs4d915t1916t1917t1 ... Show all

Table of Contents