Remote thermostat applications
•
CACG/CAHG units require a remote
thermostat for operation. CACH/CAHH
units can be operated by a remote ther-
mostat by configuring the unit's DIP
switches.
•
A thermostat can be obtained through
EMI or your local distributor.
NOTICE
Make sure the thermostat is suitable for
unit operation (i.e., cooling only, cool-
ing/electric heat, heat pump.) See ther-
mostat requirements in this manual.
Mechanical characteristics
Filters
•
Metal framed filters are fitted. These are
reusable and may be vacuum cleaned.
Condensate pump
•
A condensate pump is designed to carry
water out of the unit. The pump is fixed
to a mounting bracket which can be
withdrawn from the side of the chassis
and incorporates an inspection hole to
allow a visual check of the pump during
operation. A float switch stops the cool-
ing action (shuts off the compressor)
should the pump become blocked or fail.
(Important: Total lift for this pump is 36"
(0.9 m) or less.)
Comfort where it counts
CACG/CAHG & CACH/CAHH
• Installation, Operation and Maintenance Manual •
Verify Unit Before Installing
(continued)
Air vanes
•
Air outlet vanes are manually adjustable
on the models 9 and 12 or driven by an
electric motor on the models 24 and 36.
•
Where fitted, the motorized air vanes can
be set to auto sweep or can be stopped in
a fixed position.
Heating
•
The cassette may be fitted with electric
heaters which are equipped with over-
temperature limit switches. Consult
factory for available models with electric
heat.
Fresh air connection
•
Fresh air may be introduced to the unit
by the addition of ducts connected to the
fresh air knockouts on the cassette case.
•
Recommended maximum length is 10'
(3m) of 4" (0.1m) diameter duct. The
fresh air volume is approximately 7–10%
of the unit's published maximum air flow
(if more than 10% make up air is needed,
a fresh air booster fan is required).
•
Refer to Performance Data section of this
manual for further information.
•
The cassette is best installed in new con-
struction or existing construction with a
suspended or false ceiling with enough
clearance to accommodate concealing
the piping and electrical connections to
the unit.
6
Air Handlers
P/N 240007756, Rev. A [051509]