Remote thermostat applications
CACG/CAHG units require a remote
thermostat for operation. CACH/CAHH
units can be operated by a remote ther-
mostat by configuring the unit's DIP
switches.
A thermostat can be obtained through
EMI or your local distributor.
NOTICE
Make sure the thermostat is suitable for
unit operation (i.e., cooling only, cool-
ing/electric heat, heat pump.) See ther-
mostat requirements in this manual.
Mechanical characteristics
Filters
Metal framed filters are fitted. These are
reusable and may be vacuum cleaned.
Condensate pump
A condensate pump is designed to carry
water out of the unit. The pump is fixed
to a mounting bracket which can be
withdrawn from the side of the chassis
and incorporates an inspection hole to
allow a visual check of the pump during
operation. A float switch stops the cool-
ing action (shuts off the compressor)
should the pump become blocked or fail.
(Important: Total lift for this pump is 36"
(0.9 m) or less.)
Comfort where it counts
CACG/CAHG & CACH/CAHH
• Installation, Operation and Maintenance Manual •
Verify Unit Before Installing
(continued)
Air vanes
Air outlet vanes are manually adjustable
on the models 9 and 12 or driven by an
electric motor on the models 24 and 36.
Where fitted, the motorized air vanes can
be set to auto sweep or can be stopped in
a fixed position.
Heating
The cassette may be fitted with electric
heaters which are equipped with over-
temperature limit switches. Consult
factory for available models with electric
heat.
Fresh air connection
Fresh air may be introduced to the unit
by the addition of ducts connected to the
fresh air knockouts on the cassette case.
Recommended maximum length is 10'
(3m) of 4" (0.1m) diameter duct. The
fresh air volume is approximately 7–10%
of the unit's published maximum air flow
(if more than 10% make up air is needed,
a fresh air booster fan is required).
Refer to Performance Data section of this
manual for further information.
The cassette is best installed in new con-
struction or existing construction with a
suspended or false ceiling with enough
clearance to accommodate concealing
the piping and electrical connections to
the unit.
6
Air Handlers
P/N 240007756, Rev. A [051509]