CACH/CAHH Remote Thermostat Operation
Electric heat operation
The remote thermostat will control the call for
electric heat operation (on or off) through the
low-voltage terminals "R" and "W".
1.
After connecting the thermostat to the
unit, place the system switch in Heating
mode.
2.
Adjust the setpoint temperature above the
room temperature.
3.
The electric heat will energize along with
the indoor fan motor.
4.
Heating will continue as long as the set-
point remains above room temperature.
5.
Place the set-point temperature below
room temperature.
6.
The electric heater will switch off and the
indoor fan will remain on for an additional
sixty seconds.
NOTICE
Once the cooling has cycled off or fol-
lowing a power outage, the compressor
will not restart for at least three minutes
(anti-short-cycle timer).
Optional Heat pump with Electric
heat (Two-stage heating)
The remote thermostat will control the call
for electric heat operation (on or off) through
the low-voltage terminals "R" and "W" and
for compressor (heat pump) heating through
terminals "R" and "Y".
7.
After connecting the two (2) stage heating
thermostat to the unit, place the system
switch in Heating mode.
8.
Adjust the setpoint temperature above the
room temperature.
9.
The compressor and fan motors will start
and heating will begin.
10.
Depending on the thermostat selected,
electric heat will also energize when the
deviation between room temperature
and setpoint temperature is high enough
Comfort where it counts
CACG/CAHG & CACH/CAHH
• Installation, Operation and Maintenance Manual •
to call for second stage heating. (See
the thermostat owner's manual for this
feature).
11.
Place the setpoint temperature below the
room temperature.
12.
The outdoor Heat Pump unit and electric
heat will stop while the indoor fan will re-
main on for an additional sixty seconds.
Clean Filter Alarm (Remote
Thermostat mode)
To aid in filter maintenance, the cassette con-
troller will indicate when a scheduled filter
cleaning is required by flashing the Timer/
Alarm LED.
During normal operation, the microprocessor
will keep track of the unit's run time.
When the clean filter time has elapsed,
the Timer/Alarm LED will flash four
times to indicate that the filter needs to
be cleaned.
For remote thermostat operation, the
default clean filter time is 1000 hours.
Also, if an evaporator freeze condition
is detected four times within a 24-hour
period, the Clean Filter Alarm will appear
on the cassette display.
After filter maintenance has been performed,
press the Clear Filter Warning Button for three
seconds. The control will respond with a beep
to indicate that the timer has been reset.
46
Air Handlers
(continued)
P/N 240007756, Rev. A [051509]