Veris Industries E50H2A Installation Manual page 25

Compact power and energy meters with bacnet ms/tp support
Table of Contents

Advertisement

Installation Guide
Power Monitoring
E50H2A, E50H5A
BACnet Programming Information (cont.)
#
Object_Name
Description
AI43
KWH_B
Real Energy
Consumption
Phase B
AI44
KWH_C
Real Energy
Consumption
Phase C
AI45
Max_Power
Theoretical
Maximum System
Power
AI46
Reserved_AI46
Reserved
AI47
Energy Resets
Count of Energy
Accumulator Resets
AI48
Reserved_AI48
Reserved
AI49
Reserved_AI49
Reserved
AI50
Power Up Count
Power Up Counter
AI51
Ouput Config
Ouput Configuration
AI52
Alarm_Bitmap
Alarm_Bitmap
Binary_Input Objects
Use the Present_Value properties of the Binary_Input objects as alerts for conditions of potential concern regarding to the system measurement. These values are dynamic
and are not latched, so if the condition is resolved, the alert goes inactive, whether it has been read or not.
These objects support the Description and Reliability object properties and all required Binary_Input object properties. None of them are writable. For complete assurance,
check the Reliabilty property for a No_Fault_Detected status before reading the Present_Value.
To test the meter's alert status, read the Present_Value of each of the Binary_Input objects representing the alert bits of interest, or read the Present_Value of AI52, which
combines all these bits into a single decimal value. AI52 represents the status of all 14 or 15 Binary_Object alert values in one number that can be read without having to
access mulitple objects. The bit value of Object BI1 is the least significant bit and BI14 or BI15 is the most significant bit (BI15 is only present on the E50H5A).
#
Name
BI1
Volts_Error_A
Voltage Out of Range Phase A
BI2
Volts_Error_B
Voltage Out of Range Phase B
BI3
Volts_Error_C
Voltage Out of Range Phase C
BI4
Current_Error_A
Current Out of Range Phase A
BI5
Current_Error_A
Current Out of Range Phase B
BI6
Current_Error_A
Current Out of Range Phase C
BI7
Frequency_Error
Frequency Error
ZL0117-0D
Page 25 of 28
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
R/W
NV
Units
R
NV
kWh
0 - 3.4+E38
R
NV
kWh
0 - 3.4+E38
R
NV
kW
0 - 1.84467e19
R
R
NV
0 - 32767
R
R
R
NV
0 - 32767
R
NV
0 - 15
R
0 - 32767
Description
R/W
R
0=INACTIVE, 1=ACTIVE
R
0=INACTIVE, 1=ACTIVE
R
0=INACTIVE, 1=ACTIVE
R
0=INACTIVE, 1=ACTIVE
R
0=INACTIVE, 1=ACTIVE
R
0=INACTIVE, 1=ACTIVE
R
0=INACTIVE, 1=ACTIVE
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Range
Range
Phase A Input Voltage exceeds meter's measurement range
Phase B Input Voltage exceeds meter's measurement range
Phase C Input Voltage exceeds meter's measurement range
Phase A Current out of range
Phase B Current out of range
Phase C Current out of range
Phase A Frequency out of range
Additional information
Theoretical Maximum System Power – This is the
theoretical maximum power the meter expects to see
on a service. It is calculated by the meter from the
System Type (in object AV2), CT Size (in object AV3),
and System Voltage (in object AV6) - Power Factor is
assumed to be unity. The register is updated whenever
the user changes any of these parameters.
Returns QNAN or any value
Running count of how many times the energy counter
has been reset
Returns QNAN or any value
Returns QNAN or any value
Running count of product power-up cycles (Control
Power)
E50H2A returns "11"
E50H5A returns "10"
This contains a decimal value that represents the status
of all Binary_Object alert values in one number that
can be read without having to access mulitple objects
(the E50H2A has 14 values, the E50H5A has 15). It is a
decimal representation of a 14-bit or 15-bit hexidecimal
value produced by combining the alert bits into one
number, where the bit value of Object BI1 is the least
significant bit and BI14 or BI15 is the most significant
bit.
Additional information