Installation Guide
Power Monitoring
E50H2A, E50H5A
BACnet Programming Information (cont.)
#
Object_Name
Description
AI26
kVAh
Apparent Energy
Consumption
AI27
kVARh
Reactive Energy
Consumption
AI28
kVA_A
Apparent Power
Phase A
AI29
kVA_B
Apparent Power
Phase B
AI30
kVA_C
Apparent Power
Phase C
AI31
KVAR_A
Reactive Power
Phase A
AI32
KVAR_B
Reactive Power
Phase B
AI33
KVAR_C
Reactive Power
Phase C
AI34
KW_Present_
Total Real Power
Demand
Present Demand
AI35
KVAR_Present_
Total Reactive Power
Demand
Present Demand
AI36
KVA_Present_
Total Apparent Power
Demand
Present Demand
AI37
KW_Max_
Total Real Power
Demand
Maximum Demand
AI38
KVAR_Max_
Total Reactive Power
Demand
Maximum Demand
AI39
KVA_Max_
Total Apparent Power
Demand
Maximum Demand
AI40
E50H2: Pulse
E50H2: Pulse Count
Count
E50H5: Pulse Count
E50H5: Pulse_
#1
Count_1
AI41
E50H2: Reserved
E50H2: Reserved
E50H5: Pulse_
E50H5: Pulse Count
Count_2
#2
AI42
KWH_A
Real Energy
Consumption
Phase A
ZL0117-0D
Page 24 of 28
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
R/W
NV
Units
R
NV
kVAh
0 - 3.4+E38
R
NV
kVARh
0 - 3.4+E38
R
kVA
0 - Max_Power (AI45)
R
kVA
0 - Max_Power (AI45)
R
kVA
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
R
kW
0 - Max_Power (AI45)
R
kVAR
0 - Max_Power (AI45)
R
kVA
0 - Max_Power (AI45)
R
NV
kW
0 - Max_Power (AI45)
R
NV
kVAR
0 - Max_Power (AI45)
R
NV
kVA
0 - Max_Power (AI45)
R
NV
#
0 - 4294967040
R
NV
#
0 - 4294967040
R
NV
kWh
0 - 3.4+E38
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Range
The UNITS property of object AI26 reports that these units
are kWh because there is no unit type in the BACnet
standard for kVAh.
The UNITS property of object AI27 reports that these units
are kWh because there is no unit type in the BACnet
standard for kVARh.
This retains the largest value measured for Total Real
Power Demand (AI34) for any single demand interval
since the Max Demand were last explicitly reset via
AV1 (this is also reset when the demand interval is
changed).
This retains the largest value measured for Total Reactive
Power Demand (AI35) for any single demand interval
since the Max Demand were last explicitly reset via
AV1 (this is also reset when the demand interval is
changed).
This retains the largest value measured for Total Apparent
Power Demand (AI36) for any single demand interval
since the Max Demand were last explicitly reset via
AV1 (this is also reset when the demand interval is
changed).
Running count of contact closures on Pulse1 input since
last reset. Write 16498 (0x4072) to the Present_Value
property of Analog_Value object AV1 to reset both
Pulse Counters to 0.
E50H2A: Reserved
E50H5A: Pulse Count 2; Running count of contact closures
on Pulse2 input since last reset. Write 16498 (0x4072)
to the Present_Value property of Analog_Value object
AV1 to reset both Pulse Counters to 0.