Veris Industries E50H2A Installation Manual page 2

Compact power and energy meters with bacnet ms/tp support
Table of Contents

Advertisement

Installation Guide
Power Monitoring
E50H2A, E50H5A
Specifications
(cont.)
ZL0117-0D
Page 2 of 28
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
DC*
Ride Through Time
Pulse
Minimum Pulse Width
Alarm Contacts (E50H2 only)
RS-485 Port
Weight
IP Degree of Protection
(IEC 60529)
Display Characteristics
Terminal Block Screw Torque
Terminal Block Wire Size
Rail
Operating Temperature Range
Storage Temperature Range
Humidity Range
Altitude of Operation
US and Canada
Dielectric Withstand
Conducted and Radiated
Emissions
Conducted and Radiated
Immunity
US and Canada (cULus)
Europe (CE)
* External DC current limiting is required, see fuse recommendations.
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
CONTROL POWER
AC
5 VA max.; 90V min.
UL Maximums: 600V
(347V
L-L
3 W max.; UL and CE: 125 to 300VDC
100 msec at 120VAC
INPUT
Solid-state or mechanical contacts (current less than 1 mA);
E50H2: 1 pulse input; E50H5: 2 pulse inputs)
20 msec
OUTPUT
N.C., static output; (30VAC/DC, 100mA max.@25°C, derate 0.56mA
per °C above 25°C)
2-wire, 9600 to 115.2 kbaud, BACnet MS/TP
MECHANICAL CHARACTERISTICS
0.62 lb (0.28 kg)
IP40 front display; IP20 Meter
Back-lit blue LCD
0.37 to 0.44 ft-lb (0.5 to 0.6 N·m)
26 to 14 AWG (0.13 to 2.08 mm
T35 (35mm) DIN Rail per EN50022
OPERATING CONDITIONS
-30° to 70°C (22° to 158°F)
-40° to 85°C (-40° to 185°F)
<95% RH noncondensing
3000 m
COMPLIANCE INFORMATION
CAT III, Pollution degree 2;
for distribution systems up to 347V
CE
CAT III, Pollution degree 2;
for distribution systems up to 300V
Per UL 508, EN61010
FCC part 15 Class B, EN55011/EN61000 Class B (residential and light
industrial)
EN61000 Class A (heavy industrial)
UL508 (open type device)/CSA 22.2 No. 14-05
EN61010-1
); CE Maximum: 300V
L-N
L-N
)
2
/600VAC
L-N
L-L
L-N
TM
08131

Advertisement

Table of Contents
loading

This manual is also suitable for:

E50h5a

Table of Contents