Veris Industries E50H2A Installation Manual page 15

Compact power and energy meters with bacnet ms/tp support
Table of Contents

Advertisement

Installation Guide
Power Monitoring
E50H2A, E50H5A
UI for Setup (cont.)
To Setup p. 1 "S PWR"
Back
SPLOS
Phase
Loss
Back
SDMND
Demand
Back
S DIS
Display
Units
Back
SPASS
Setup
Passwords
To Setup page 1 "S BAC"
ZL0117-0D
Page 15 of 28
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
VOLTS
IMBAL
--------
--------
0.10
0.25
Next
INTRV
--------
6
SEC
5
--------
4
00900
3
2
Next
1
UNITS
--------
IEEE
IEC
Next
SETUP
RESET
--------
--------
00000
00000
Next
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Set Phase Loss:
VOLTS - Phase Loss Voltage: The fraction of the system
voltage below which Phase Loss Alarm is on. For system
types with neutral, the Line to Neutral voltage is also
calculated and tested. If the System Voltage is 600 and the
fraction is set to 0.10, then the Phase Loss threshold will be
60 volts.
IMBAL - Phase Loss Imbalance: The fractional difference
in Line to Line voltages above which Phase Loss Alarm is
on. For system types with neutral, the Line to Neutral
voltages are also tested. For system types 1+N (10) and 2
(11) , imbalance is not tested.
Set Demand Interval:
INTRV - The number of Sub-Intervals (1 to 6) in a
Demand Interval. Default is 1 (block demand).
SEC - Sub-Interval length in seconds. Default is
900 (15 minutes). Set to 0 for external sync-to-
comms.
Set Display Units: +/- to switch between:
IEEE – VLL VLN W VAR VA Units.
IEC -
U
V
P
Q
Set Passwords:
SETUP - The Password to enter the SETUP menu.
RESET - The Password to enter the RESET menu.
S Units.