Installation
16
30 (1.2)
 3
Welding socket for pipes DN 25. Engineering unit mm (in)
Pipe ≥DN 40: With the marking (according to the nominal diameter) flush against the
outer wall of the pipe, weld the welding socket at right angles to the axis of the piping.
The DN 300 marking must be used for nominal diameters >DN 300.
30 (1.2)
 4
Welding socket for piping ≥DN 40. Engineering unit mm (in)
Installation in plastic pipe
For pipe sizes ≥DN 65, the measuring device is mounted in plastic pipes using a plastic
welding socket. The plastic welding socket can be purchased from the Georg Fischer
company. PVC, PP and PE sockets are available. Depending on the outer diameter of the
pipe, the dimension L must be adjusted accordingly by the client onsite. Perform the
following steps when installing a plastic welding socket:
NOTICE
Damage to the measuring device
Only weld the welding socket when the measuring device is not installed.
1. Determine dimension L: L = 40 - S - E.
2. Determine the welding socket taking dimension L into account.
3. Taking immersion depth E into account, weld the welding socket at right angles to
the axis of the piping.
M30 x 2
-0.10 (0.004)
-0.30 (0.01)
M30 x 2
≥DN 300
DN 250
DN 200
DN 150
DN 100
DN 80
DN 40/50
-0.10 (0.004)
-0.30 (0.01)
Magphant
27 mm
23 (0.9)
27 mm
30 (1.2)
Endress+Hauser
A0040150
A0040151