100
REM _____________________________________________________________
101
REM __
This program inputs a parameter number and a value
102
rem __ from a user terminal and writes it out to a scanport
103
rem __ compatible device.
104
rem __ for 1746–BAS and 1203–GD2 modules
105
rem _____________________________________________________________
110
STRING 512,127
140
REM
150
REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
160
REM Setup port 1 to 9600 baud, no parity, 8 bits, 1 stop bit,
170
REM software handshaking, and battery backed ram data storage.
180
REM
!!!!REMEMBER TO SET TERMINAL TO MATCH!!!!
190
REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
200
MODE (PRT1,9600,N,8,1,S,R)
210
REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
220
REM
230
REM Setup port 2 to 300 baud, no parity, 8 bits, 1 stop bit,
240
REM software handshaking, and battery backed ram data storage.
250
REM
260
REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
270
MODE (PRT2,300,N,8,1,S,R)
280
REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
290
REM
300
REM Enable DF1 driver
310
REM (20
= Setup for Full Duplex, Auto–Detect Embedded Responses,
320
REM
Disable Duplicate Packet Detection, BCC error checking)
330
REM (200 = Wait 1 second for polling by Master)
340
REM (2
= 2 retries)
350
REM (0= No RTS on delay)
360
REM (0
= No RTS off delay)
370
REM (8
= 1746–BAS module address)
380
REM ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
390
PUSH 20
400
PUSH 200
410
PUSH 2
420
PUSH 0
430
PUSH 0
440
PUSH 8
450
CALL 108
460
REM __________________ end df1 config _____________________________
461
Print: print "A negative parameter number exits the program
470
INPUT "Offset (Parameter Number)?
475
IF (PAR_NUM<0) THEN
480
INPUT "Control (parameter value)?
481
REM encode the value as an ASCII hex string in order of LOW, HIGH
490
ASC($(1),1)=PAR_VALUE–(INT(PAR_VALUE/256)*256)
500
ASC($(1),2)=INT(PAR_VALUE/256)
510
GOSUB 550 :
REM fire off the write instruction
520
GOTO 460
530
CALL 113
540
END
DF1 Messaging with a 1746–BAS Module Example
This example accepts a parameter number and a value from a user
terminal and writes the data out to a SCANport–compatible device.
",PAR_NUM
GOTO 530
",PAR_VALUE
Configuring and Interfacing
"