Configure Submenu
1
Output Voltage
Sync Freq Window
Bypass V Window
Bypass Condition
2
ECO Mode
Manual Bypass
Battery Test
Audible Alarms
EBM Number
Wiring Fault
NCL Control
Language
3
Generator Mode
Communication
Dry Relay Set
4
Converter Mode
Screen Saver
Clear Event Log
Button OFF LOCK
Charger Function
Signal Inputs
Charger Check
With Transformer
Backfeed Check
1
200V are derated by 20%, 208 V are derated by 10% for OL6000RT3U
2
This function can't be set when Manual Bypass, Generator Mode or Converter Mode is enabled.
3
UPS has no bypass when Generator Mode is enabled.
4
UPS has no bypass when Converter Mode is enabled. This function can only be set before the UPS is on.
SILENCING AUDIBLE ALARMS
Press any of four function buttons on the LCD module; Note: the alarm can not be turned off for a "Battery Low"
1.
condition. This condition will still result in an audible alarm.
Configure "Audible Alarms" as "Disable" on the LCD module and it will stop warning of any malfunction audibly.
2.
MANUAL BATTERY TEST
Configure "Battery Test" as "Active" on the LCD module; and it will perform the "Manual Battery Test"
Copyright © 2017 Cyber Power Systems, Inc.
LCD SETUP FUNCTIONS
Available Settings
= [200V] [208V] [220V] [230V] [240V]
Range= [+/- 1%] [+/- 2%] [+/- 3%] [+/- 4%] [+/- 5%]
[+/- 6%] [+/- 7%] [+/- 8%] [+/- 9%] [+/-10%]
Range= [+10%/-10%] [+10%/-15%] [+10%/-20%]
[+15%/-10%] [+15%/-15%] [+15%/-20%]
[Check Freq/Volt] [Check Volt Only] [No Bypass]
[Disable] [Enable]
[V Range= +/-15%] [V Range= +/-10%] (for [Enable])
[Disable] [Enable]
[Activate?]
[Disable] [Enable]
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
[Disable] [Enable]
[Outlet On] [Outlet Off]
[English] [Español-Spanish] [Fran
[Disable] [Enable]
[Disable] [Enable]
[I/P Power Fail] [Battery Low] [Summary Alarm] [UPS On Bypass] [UPS Fail]
[Converter Off] [O/P Freq = 50Hz] [O/P Freq = 60Hz]
[Disable] [1 Minutes] [5 Minutes]
[Activate?]
[Disable] [Enable]
[SBM] [Constant]
[Disable] [EPO][ROO]
[Disable] [Enable]
[Disable] [Enable]
[Disable] [Enable]
ç
ais-French] [Deutsch-German]
16
Default Setting
208V
+/- 5%
+10%/-15%
Check Freq/Volt
Disable
V Range= +/-10%
Disable
None
Enable
0
Disable
Outlet On
English
Disable
Enable
I/P Power Fail
Converter OFF
5 minutes
None
Disable
SBM
Disable
Disable
Disable
Disable