EXTENDED BATTERY MODULE FRONT/REAR PANEL DESCRIPTION
1. On-board Replaceable Fuse Cover
Replaceable fuse is accessible from the rear panel.
Service to be performed by qualified personnel only.
2. AC Circuit Breaker
Provides overload and fault protection.
3. AC Output Outlet (IEC320 C13)
Use this outlet to connect to the AC Input Inlet of a
downstream Battery module.
4. AC Input Inlet (IEC320 C14, Charge Only)
AC power connectivity to wall receptacle.
5. Input Connector
Use this input connector to daisy chain the next Battery
module. Remove the connector cover for access.
6. Output Cable
Use this output cable to connect the Battery module to the
Power module or to the next Battery module.
7. DC Breaker
Use the DC breaker to disconnect battery output.
CONNECTION #1 : POWER MODULE WITH ONE EXTENDED BATTERY MODULE
Step 1: Turn off the DC breaker of the EBM.
Step 2: Loosen the two screws to remove the battery cable
retention bracket of the power module.
Step 3: Use the output cable of the EBM to connect
to the Power module.
Step 4: Rotate the battery cable retention bracket and tighten
the two screws to fix battery cable.
Step 5: Use a power cord to plug AC input inlet of the battery
module into a wall receptacle.
Step 6: Turn on the DC breaker of the EBM.