Configuration
6.3.3
Changing the IP address of the Ethernet interfaces (X101,
X102)
DIP switches take priority
The DIP switches are set ex factory such that DHCP is active for the Ethernet interfaces (X101,
X102). As a result, the settings in the operating system or via the web interface are not adopted.
Deactivate DHCP using the DIP switches. Set the DIP switches 10 and 9 to "off" and 1 to 8 to "on"
so that the settings are adopted from the operating system or the web interface.
In this work step you will learn how to change the IP address of the Ethernet interface (X101, X102) via the
web interface (Beckhoff Device Manager).
Requirements:
• Set the DIP switches correctly so that the IP address is adopted completely from the operating system.
• Start the web interface (see: Starting the Beckhoff Device Manager).
Change the IP address as follows:
1. Click on Device and then on Connectivity.
2. Click on the wrench symbol to configure the network settings.
3. Change the network settings and assign a new IP address.
ð Save the settings to confirm all changes.