http://www.delta.com.tw/industrialautomation/
Terminal Panels Series
TP02G-AS1
Instruction Sheet
1
WARNING
Please read this manual thoroughly before using the TP02G.
DANGER! DC input power must be OFF before any maintenance. Do not connect or remove wires and
connectors while power up to the circuit. Only qualified technicians are allowed to do the maintenance.
The display panel of the TP02G is waterproof. But please keep away grease, corrosive liquids or sharp
objects from contacting the TP02G.
DANGER! The TP02G requires 24VDC input power. The 24VDC input power should not be connected to
the RS-485 communication port. The unit may be destroyed and can't be repaired if the input power is
improperly applied. Please confirm the input power wiring is correct before power up.
DANGER! An electrical charge will remain on the DC-link capacitors for 1 minute after power has been
removed. This residual power may be hazardous and the TP02G should not be worked on until this
charge has dissipated. To prevent personal injury, do not conduct any wiring or investigation on the TP02G
until 1 minute after power off. Do not touch any terminals while power is applied to the TP02.
CAUTION! Always ground the TP02G using the grounding terminal. This will not only act as a safety, but
also help filter electrical noise. The grounding method must comply with the laws of the country where the
unit is to be installed.
CAUTION! If you turn the fixed support that is packaged together with TP02G too tight, TP02G may be
damaged.
2
INTRODUCTION
2.1 Model Explanation
Nameplate
Production model
MODEL :
TP02G-AS1
Power input spec.
POWER INPUT :
24Vdc 3W
Barcode and
serial number
VX.XX
Version
TP02GAS1W6050004
DELTA ELECTRONICS, INC
Note: The words of "MADE IN XXXXX" will be different due to the manufacturing location.
Model Explanation
Serial Number Explanation
TP 02 G
-
AS 1
TP02GAS 1 W 6 05 0004
Reserved
Reserved
T: Text mode
G: Graphic mode
LCD Spec.
Series name
2.2
Outline
LCM
Display Area
Escape/Exit
Back Panel
2006-0 7-18
5011617503-2 GE3
2.3
Dimensions
Front Panel
Right Side Diagram
Back side
MADE IN XXXXXXX
Vertical View
Production serial number
Production weeks
Production year(2006)
Production plant(W:Wuijang)
Version
Production model
Mounting Panel Dimension
Alarm Indication LED
RS-232 Indication LED
RS-485 Indication LED
Function Keys
Arrow Keys
Enter Key
RS-232
Extension port
5-PIN terminals: Wire gauge: 12-24 AWG / Torque: 4.5 lb.-inch
Unit: mm[inch]
Unit: mm[inch]
Unit: mm[inch]
85
[3.35]
135~136.5[5.31~5.37]
Thickness Range 0.5~9mm
Unit: mm[inch]
Installation Method
One easy way is insert TP02G to the opening hole of panel and tight up the screws. However, if a firm mounting
TP02G to the panel is needed, please use the fixed support accessory which is packed together with TP02G, then
infix the fixed support in the back and tight up the screws.
If you turn the screw exceeds torque: 4-5(kg-cm), TP02G may be damaged.
(Note:the flat surface should be a Type 4 "Indoor Use Only" enclosure or equivalent.)
Please leave sufficient space (more than 50mm) around the unit for heat dissipation.
Thickness:
0.5~9.0mm
Panel Function Explanation
Panel Component
Explanation
Status 1: When power is on, the LED will blink slowly for three times.
Alarm Indication LED
Status 2: When there is an abnormal situation, the LED will blink quickly along with
an alarm sound.
RS-232 Indication LED
Will blink when transmitting program and communicating by using RS-232.
(Yellow)
RS-485 Indication LED
Will blink when communicating by using RS-485.
(Green)
Esc (Escape/Exit)
Used to cancel an incorrect input, or to Exit a programming step.
UP/Pg Up: Used to increase the value or move screen up one page.
Pg Dn/DOWN: Used to decrease the value or move screen down one page.
Arrow Keys
Left: Left direction key. (move curser to left)
Right: Right direction key. (move cursor to right)
Enter key
Used to input a value or accept a programming instruction.
F0/0: used as a constant 0, or user can define it as function F0.
F1/1: used as a constant 1, or user can define it as function F1.
F2/2: used as a constant 2, or user can define it as function F2.
F3/3: used as a constant 3, or user can define it as function F3.
F4/4: used as a constant 4, or user can define it as function F4.
Function Keys
F5/5: used as a constant 5, or user can define it as function F5.
F6/6: used as a constant 6, or user can define it as function F6.
F7/7: used as a constant 7, or user can define it as function F7.
F8/8: used as a constant 8, or user can define it as function F8.
F9/9: used as a constant 9, or user can define it as function F9.
3
SPECIFICATION
Electrical Specification
Item
Function Key / Digital Key
F0/0~F9/9, ESC, ENTER and ARROW keys
External Input Power
24V (3W Max.)
Memory Capacity
CPU
Hitachi HD64F3064F
RAM of System
Communication Interface
Com1: RS-232 and Com2: RS-485
Waterproof Class of Front Panel
Environment Condition
0~50℃, relative humidity 20-90% RH(non-condensing)
Storage Temperature of Hardware
TP02G-AS1
256K Byte
32K Byte
IP65/NEMA4
-20~60 °C
Need help?
Do you have a question about the Terminal Panels Series and is the answer not in the manual?