(2)

Checking the Protective Devices

Disconnect the connector, which consists of P (plug) and S (socket) when you want to
check the protective device.
Then check continuity among plug's (and/or socket's) terminal as in Fig. 46.
Normality of the protective device can be judged by the following table.
The Protective Device is proved normal if there is a continuity between terminals.
1
Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit
Disconnect the connector which leads to the indoor fan motor (FMI).
Check the socket's terminals.
2
Compressor motor thermal protector (49C) . . . . . . Outdoor unit
Disconnect both the connectors in the outdoor unit.
Check terminal between the plug and socket.
3
Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit
Disconnect both the connector which leads to the outdoor fan motor (FMO).
Check socket's terminal.
socket
Multimeter
0642_X_S
– 69 –
4. Service procedures
Fig. 46
SM830042